B.3 Parameter Table
330
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
◆
E: Motor Parameters
No.
Name
Description
Range
Def.
Control
Mode
Addr. Hex Pg.
V/f OL
V PM
E1: V/f Pattern for Motor 1
Use E1 parameters to set V/f characteristics for the motor.
E1-01
Input Voltage
Setting
This parameter must be set to the power supply voltage.
WARNING!
Drive input voltage (not motor voltage)
must be set in E1-01 for the protective features of the
drive to function properly. failure to do so may result in
equipment damage and/or death or personal injury.
155 to 255 200 V
S
S
S
300
E1-03
V/f Pattern
Selection
F: Custom V/f. E1-04 through E1-13 settings define the
V/f pattern.
F
F
A
A
−
302
E1-04
Maximum Output
Frequency
To set linear V/f characteristics, set the same values for
E1-07 and E1-09. In this case, the setting for E1-08 will
be disregarded. When E1-13 = 0.0 V, then the drive uses
the value set to E1-05 to control the voltage level. Ensure
that the four frequencies are set according to these rules:
E1-04
≥
E1-06> E1-07
≥
E1-09
40.0 to
400.0
50.0 Hz
S
S
S
303
E1-05
Maximum Voltage
0.0 to 255.0
200.0 V
S
S
S
304
E1-06
Base Frequency
0.0 to E1-
04
50.0 Hz
S
S
S
305
E1-07
Middle Output
Frequency
0.0 to E1-
04
2.5 Hz
A
A
−
306
E1-08
Middle Output
Frequency Voltage
0.0 to 255.0
16.0 V
A
A
−
307
E1-09
Minimum Output
Frequency
0.0 to E1-
04
1.3 Hz
S
S
S
308
E1-10
Minimum Output
Frequency Voltage
0.0 to 255.0
12.0 V
A
A
−
309
E1-11
Middle Output
Frequency 2
0.0 to E1-
04
0.0 Hz
A
A
−
30A
E1-12
Middle Output
Frequency Voltage
2
0.0 to 255.0
0.0 V
A
A
−
30B
E1-13
Base Voltage
0.0 to 255.0
0.0 V
A
S
−
30C
E2: Motor Parameters
Use E2 parameters to set motor-related data.
E2-01
Motor Rated
Current
Sets the motor nameplate full load current in amperes
(A).
Automatically set during Auto-Tuning.
10 to 200%
of drive
rated
current
S
S
−
30E
E2-02
Motor Rated Slip
Sets the motor rated slip in Hertz.
Automatically set during rotational Auto-Tuning.
0.00 to
20.00
A
A
−
30F
E2-03
Motor No-Load
Current
Sets the magnetizing current of the motor in Ampere.
Automatically set during rotational Auto-Tuning.
0 to less
than E2-01
A
A
−
310
E2-04
Number of Motor
Poles
Sets the number of motor poles. Automatically set during
Auto-Tuning.
2 to 48
4 poles
A
A
−
311
E2-05
Motor Line-to-Line
Resistance
Sets the phase-to-phase motor resistance in ohms.
Automatically set during Auto-Tuning.
0.000 to
65.000
A
A
−
312
E2-06
Motor Leakage
Inductance
Sets the voltage drop due to motor leakage inductance as
a percentage of motor rated voltage.
Automatically set during Auto-Tuning.
0.0 to 40.0
A
A
−
313
E2-07
Motor Iron-Core
Saturation
Coefficient 1
Sets the motor iron saturation coefficient at 50% of
magnetic flux. Automatically set during Auto-Tuning.
0.00 to 0.50 0.50%
−
A
−
314
E2-08
Motor Iron-Core
Saturation
Coefficient 2
Sets the motor iron saturation coefficient at 75% of
magnetic flux. Automatically set during Auto-Tuning.
[E2-07] to
0.75
0.75%
−
A
−
315
E1-09 E1-07 E1-06 E1-11 E1-04
E1-05
E1-12
E1-13
E1-08
E1-10
VACrms Out(V)
Frequency (Hz)