6.6 Operator Programming Errors
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
265
Tr
ouble
sho
ot
in
g
6
In PM Open Loop Vector Control, parameters E5-02 to E5-07 are set to
0.
• Set the correct motor code in accordance with the motor being used
(E5-01).
• When using a special-purpose motor, set E5-
in accordance with
the Test Report provided.
The following conditions are true in PM Open Loop Vector Control:
• E5-03 does not equal 0
• E5-09 and E5-24 are both equal to 0, or neither equals 0
• Set E5-09 or E5-24 to the correct value, and set the other to “0”.
• Set the motor-rated current for PM to “0” (E5-03).
Note:
Use U1-18 to find which parameters are set outside the specified setting range. Other errors are given precedence over oPE08 when multiple
errors occur at the same time.
LED Operator Display
Error Name
oPE09
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is
enabled (b5-01 = 1 to 4).
Cause
Possible Solutions
The following simultaneous contradictory settings:
• b5-15 not 0.0 (PID Sleep Function Operation Level)
• The stopping method is set to either DC injection braking or coast to
stop with a timer (b1-03 = 2 or 3).
• Set b5-15 to another value besides 0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = “0”
or “1”).
PID control is set to b5-01 = 1 or 2, but the lower limit for the frequency
reference (d2-02) is not set to 0 while reverse output is enabled (b5-11 =
1).
Correct the parameter settings.
PID control is set to b5-01 = 3 or 4, but the lower limit for the frequency
reference (d2-01) is not 0.
LED Operator Display
Error Name
oPE10
V/f Data Setting Error
The following setting errors have occurred where: E1-04 is greater than
or equal to E1-06 is greater than or equal to E1-07 is greater than or
equal to E1-09.
Or the following setting errors have occurred: E3-04 is greater than or
equal to E3-06 is greater than or equal to E3-07 is greater than or equal
to E3-09.
Cause
Possible Solutions
—
Correct the settings for E1-04, E1-06, E1-07, and E1-09 (or E3-04, E3-
06, E3-07, and E3-09 for motor 2).
LED Operator Display
Error Name
oPE11
Carrier Frequency Setting Error
The carrier frequency is set to the wrong value.
Cause
Possible Solutions
The following simultaneous contradictory settings: C6-05 is greater than
6 and C6-04 is greater than C6-03 (carrier frequency lower limit is
greater than the upper limit). If C6-05 is less than or equal to 6, the drive
operates at C6-03.
Correct the parameter settings.
Upper and lower limits between C6-02 and C6-05 contradict each other.
LED Operator Display
Error Name
oPE13
Pulse Monitor Selection Error
Incorrect setting of monitor selection for Pulse Train (H6-06).
Cause
Possible Solutions
Scaling for the Pulse Train monitor is set to 0 (H6-07 = 0) while H6-06 is
not set to 000, 031, 101, 102, 105, or 116.
Change scaling for the Pulse Train monitor or set H6-06 to 000, 031,
101, 102, 105, or 116.