B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
421
Pa
ra
met
e
r Li
st
B
n
U9: KEB Voltage Monitors
U6-25
(6BH)
Feedback Control Output
Output monitor for the ASR speed loop.
10 V: Motor
secondary rated
current
0.01%
–
U6-26
(6CH)
Feed Forward Control Output
Output monitor for Feed Forward control.
10 V: Motor
secondary rated
current
0.01%
–
U6-54
(74EH)
ACR Id Deviation Integral
Monitors the value of the ACR Id deviation integral.
10 V: 100%
0.10%
–
U6-55
(74FH)
ACR Id Deviation
Proportional
Monitors the value of the ACR Id deviation proportional.
10 V: 100%
0.10%
–
U6-57
(7C4H)
Integrated Current Deviation
during Judging Polarity
Displays the deviation from the integrated current when judging motor polarity. If this value is
lower than 819, then increase the value set to n8-84. The value 8192 is equivalent to the motor
rated current.
No signal output
available
1
–
U6-80 to
U6-99
(7B0 to 7F9H)
Option Monitors 1 to 20
Displays the data select for option monitors 1 through 20.
–
–
–
<15> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
No. (Addr.)
<15> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Name
Description
Analog Output
Level
Unit
Page
U9-01
(820H)
KEB Start Voltage
DC bus voltage value used as KEB trigger level.
No signal output
available
1 Vdc
–
U9-02
(821H)
KEB End Voltage
DC bus voltage used as KEB end level.
No signal output
available
1 Vdc
–
U9-03
(822H)
KEB Function Limit
Monitor
Displays a 5 digit number if the KEB start or end levels exceed the allowable range. If the first
is “1”, then the KEB start voltage exceeded the 150 - 400 V internal limit. If the second digit is
“1”, then the KEB end voltage exceeds the internal limit of 150 - 400 V.
No signal output
available
–
–
U9-04
(823H)
Detected Motor Speed
(Synchronous Operation)
Displays the motor speed detected by the Synchronous Operation Function (b3-24 = 3).
10 V: Max frequency
0.01 Hz
–
U9-05
(824H)
Detected Motor Residual
Voltage (Synchronous
Operation)
Displays the residual voltage detected by the Synchronous Operation Function (b3-24 = 3).
10 V: 200 Vms
0.1 Vac
–
No. (Addr.)
Name
Description
Analog Output
Level
Unit
Page
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
All Modes
All Modes
All Modes
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV