6.3 Drive Alarms, Faults, and Errors
274
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
n
Minor Faults and Alarms
give an overview of possible alarm codes. As conditions such as overvoltage can trip both a fault and alarm, it
is important to distinguish between faults and alarms in order to find the right corrective action.
If an alarm is detected, the ALM LED will blink and the alarm code display flashes. The majority of alarms will trigger a
digital output programmed for alarm output (H2-
= 10). If the ALM LED lights without blinking, this means that a
fault has been detected (not an alarm). Information on fault codes can be found in
Table 6.10 Minor Fault and Alarm Displays
FbH
Excessive PID Feedback
rF
Braking Resistor Fault
FbL
PID Feedback Loss
rH
Dynamic Braking Resistor
GF
Ground Fault
rr
Dynamic Braking Transistor
LF
Output Phase Loss
SC
Output Short-Circuit or IGBT Fault
LF2
Current Imbalance
SEr
Too Many Speed Search Restarts
LSo
LSo Fault
STo
Pull-Out Detection
nSE
Node Setup Error
SvE
Zero-Servo Fault
oC
Overcurrent
UL3
Undertorque Detection 1
oFA00
Option Card Connection Error (CN5-A)
UL4
Undertorque Detection 2
oFA01
Option Card Fault (CN5-A)
Uv1
Undervoltage
oFA02
Option Card Fault (CN5-A)
Uv2
Control Power Supply Undervoltage
to
oFA03 to oFA06
Option Card Error (CN5-A)
Uv3
Soft Charge Circuit Fault
voF
Output Voltage Detection Fault
,
oFA10, oFA11
Option Card Error (CN5-A)
–
–
–
–
<1> Displays
or
if a control circuit error occurs while the drive is starting up.
Displays
or
if a control circuit error occurs mid-operation.
Digital Operator Display
Name
Minor Fault Output
(H2-
= 10)
Page
LED Operator
LCD Operator
bb
Drive Baseblock
No output
boL
Braking Transistor Overload Fault
YES
bUS
Option Card Communications Error
YES
CALL
Serial Communication Transmission Error
YES
CE
MEMOBUS/Modbus Communication Error
YES
CrST
Cannot Reset
YES
dEv
Excessive Speed Deviation (for Control Mode with PG)
YES
dnE
Drive Disabled
YES
EF
Run Command Input Error
YES
EF0
Option Card External Fault
YES
to
EF1 to EF8
External Fault (input terminal S1 to S8)
YES
FAn
Internal Fan Fault
YES
FbH
Excessive PID Feedback
YES
FbL
PID Feedback Loss
YES
Digital Operator Display
Name
Page
Digital Operator Display
Name
Page
LED Operator
LCD Operator
LED Operator
LCD Operator