background image

Installation and Operation Guide SOLECTRIA XGI 1500 (Rev E, 5 Mar. 2021) 

 

 

58 of 70 

 

Regular Preventative Maintenance 

Solectria’s warranty terms require regular preventative maintenance. It is recommended to perform this 
service annually, adjusting the service interval as needed depending on site conditions. It may be 
necessary to perform the preventative maintenance more frequently during the first year to determine the 
appropriate service interval. 

  The wiring box requires visual inspection and thermography, and  

  The cooling system needs to be clean of debris to operate properly.  

Performing these preventative activities will help ensure proper inverter operation, avoid preventable 
failures, and extend the useful life of the inverter. Inverter damage or failure attributed to a lack of regular 
preventative maintenance may not be covered by the product warranty. 

 

9.2.1 

Thermography and Visual Inspections 

Thermography and visual inspection of the inverter’s wiring box may identify issues before a failure 
occurs. Use a thermal camera to inspect components in the wiring portion of the inverter after the 
inverter has been running for at least an hour. (Refer to Figure 7.1) 

1.  Allow the inverter to run for at least an hour above 50% power before performing thermography 

2.  Turn off the inverter, first by setting the DC Switch on the inverter to the “OFF” position, then by turning 

the AC Switch on the inverter to the “OFF” position. 

3.  Remove the 10 screws securing the wiring box cover, and set the cover aside. 

4.  Use a thermal camera to inspect for excessive temperatures of the AC terminations, DC terminations, 

busbar between the AC contactors, and AC filter terminals. Record the ambient temperature. Each 
component’s temperature must be less than the sum of the ambient temperature plus the maximum 
temperature rise above ambient value.  Each component’s temperature must also be less than the 
maximum temperature value. If any of the components in Table 9-4 Component Temperature Limits 
exceed their temperature limits or vary more than 10

°

C amongst the three phases, please contact 

Solectria Technical Support for further assistance. 

 

Component 

Maximum Temp. Rise 
above Ambient 

Temperature Maximum 

AC or DC Termination 

50

°

90

°

AC Contactor Busbar 

55°C 

95

°

EMI Filter Terminals 

40°C 

90

°

Table 9-4 Component Temperature Limits 

 

  

Summary of Contents for SOLECTRIA XGI 1500-166/166-3S

Page 1: ...cial 1500VDC String Inverter SOLECTRIA XGI 1500 Installation and Operation Guide Models XGI 1500 125 125 UL XGI 1500 125 150 UL XGI 1500 150 166 UL XGI 1500 166 166 UL XGI 1500 125 125 3S XGI 1500 166 166 3S ...

Page 2: ...ansformer Configuration 19 Equipment Grounding 20 AC Connections 22 AC Breaker Specifications 23 DC Connections 24 DC Connection Using the XGI Remote or Attachable Combiner 25 DC Connection Using the XGI Attachable Combiner Box 27 Conduit Sealing 29 Antenna Mounting 30 Replace Wiring Box Cover 30 Startup and Verification Test 31 Startup Checklist 31 Startup Steps 31 Commissioning Test 32 Communica...

Page 3: ...dates 50 Automatic Remote Firmware Updates 50 Manual Firmware Updates Locally 50 Manual Firmware Updates Remote Server 50 Manual Firmware Updates Remote Access Portal 50 Communication Commissioning 52 Communication Commissioning Checklist 52 Maintenance and Troubleshooting 53 Event Codes 53 Regular Preventative Maintenance 58 Specifications 62 General Specifications 62 Enclosure 62 Voltage and Fre...

Page 4: ...ry or death CAUTION indicates a hazardous situation which if not avoided will result in minor or moderate injury NOTICE indicates a hazardous condition which if not avoided could result in equipment working abnormally or property loss INFO indicates important supplementary information to use the product effectively Symbols on Labels Table 1 2 Explanation of Symbols AC Signal DC Signal Equipment Gr...

Page 5: ...y contact components with hazardous voltage and energy Use proper safety equipment including Personal Protective Equipment PPE when de energizing the unit De energize the unit wait 5 minutes and verify the absence of voltage before opening the equipment or removing any protective shields General Damage to Equipment Attempting to service the inverter improperly may result in damage Contact Yaskawa ...

Page 6: ...l Ready Yellow On Inverter is initialized and ready to operate Off Inverter is not ready to operate Network and Communication Yellow On Network and communication services are working properly Off Network and communication services are offline Power Yellow On Inverter is generating AC power Off Inverter is not generating AC power Maintenance Yellow On Inverter needs maintenance or service Off Inver...

Page 7: ...ology o Max efficiency 99 0 o CEC efficiency 98 5 Grid adaptability o Supports multiple grid standards o Certified to UL1741SA for CA Rule 21 compliance o Adjustable reactive power o Adjustable power factor PF 0 85 o Remote power curtailment Ethernet connectivity Wi Fi accessible user interface Protective enclosure NEMA 4X rated enclosure allows for outdoor use Flexible design The SOLECTRIA XGI 15...

Page 8: ...n AC output o Internal ambient temperature o IGBT module temperature 2 1 3 Communication Overview Users can communicate with the SOLECTRIA XGI 1500 using a Wi Fi enabled smart device such as a laptop tablet or smartphone The SOLECTRIA XGI 1500 monitors internal variables which are sent via a modem or gateway to the Internet cloud In the cloud these data are stored on the SRV server where they can ...

Page 9: ...Installation and Operation Guide SOLECTRIA XGI 1500 Rev E 5 Mar 2021 9 of 70 2 1 4 Inverter Features Figure 2 3 SOLECTRIA XGI 1500 Inverter Features Front Left Right Side Right and Bottom Bottom ...

Page 10: ...y of the inverter it is recommended to mount the inverter out of the direct sunlight Inverter Facing Direction It is recommended to install the inverter facing north to minimize direct sun exposure Figure 2 4 Inverter Environment Left to Right Direct Sunlight Shaded and Rain Mount the inverter vertically and level to the ground Do not install the inverter in a pitched tilted angled orientation Fig...

Page 11: ...ter from its crate and properly dispose of the packaging material 2 Secure the inverter to the structure carefully observing the lifting hazard below Lifting Heavy Object Hazard Proper lifting technique must be used in order to avoid injuries Lift into place with at least two people or using a mechanical aid 3 Turn off the upstream AC breaker and apply a lock 4 Turn off the AC switch on the invert...

Page 12: ...gure 3 4 Ensure that the strut channel structure is capable of supporting 270 lbs 122 kg plus an effective safety margin Structural integrity of the strut structure is the responsibility of the installer Space the inverters no closer than shown in Figure 3 2 for thermal exhaust and wiring clearance Keep this area free from debris vegetation and other obstructions Figure 3 2 Inverter Minimum Spacin...

Page 13: ...n bolts not provided to connect the bottom brackets to the strut channel Figure 3 3 Mounting Holes Rear View Attach the inverter with its mounting brackets in place to the strut channel as shown in Figure 3 54 The top brackets fit over the upper strut bar to hang the inverter while securing the upper and lower brackets to the strut channel The brackets are attached to the inverter in the factory F...

Page 14: ...h the holes provided in the top face of the upper brackets and two more through the front face of the lower bracket Figure 3 5 Inverter Mounted to Strut Channels Back View Upper Image and Top View Lower Image Lifting Heavy Object Hazard Proper lifting technique must be used in order to avoid injuries Lifting requires at least two people or a mechanical hoist to install the Inverter Slotted Holes f...

Page 15: ...bottom of the inverter Remove the gland plate before drilling or punching holes to prevent metal debris from entering the inverter enclosure Re attach the gland plate to install conduit fittings and conduit Keep AC and DC connections in separate conduit All conduit used for connections must use rain tight or wet location connectors that comply with UL 514B to maintain the enclosure s Type 4X ratin...

Page 16: ...ons are complete replace all 10 screws and torque to 25 in lbs 2 8 Nm All modifications to the conduit panel must be contained within the region shown in Figure 3 8 For inverters paired with the attachable combiner box the removable conduit panels for each require a 2 hole to accommodate the provided conduit and wire assembly Modify the removable panels so this hole is located as shown in Figure 3...

Page 17: ...Installation and Operation Guide SOLECTRIA XGI 1500 Rev E 5 Mar 2021 17 of 70 Figure 3 8 Removable Conduit Panel Entry Locations ...

Page 18: ...ion and Operation Guide SOLECTRIA XGI 1500 Rev E 5 Mar 2021 18 of 70 Figure 3 9 DC Conduit Hole Location for Inverters Paired with Attachable Combiners Figure 3 10 Conduit Hole Location for Attachable Combiners ...

Page 19: ...erter must be connected to an isolation transformer provided by the customer that has a grounded Wye configuration on the inverter side see Figure 3 11 The neutral of this transformer must be grounded Figure 3 11 Permitted Transformer Configurations The inverter cannot operate connected to a delta service corner grounded service or wye with fully insulated Neutral For more information please refer...

Page 20: ...N m On the exterior of the inverter is an M6 threaded insert Figure 3 13 Torque this customer supplied fastener to 39 in lbs 4 4N m Figure 3 13 Ground Connection Inside and Outside Inverter Table 3 1 Grounding and Bonding Connection Specifications Improper Transformer Configuration Inverter will not run and may have hazardous current Connect transformer in specified configurations only Incorrect t...

Page 21: ...Installation and Operation Guide SOLECTRIA XGI 1500 Rev E 5 Mar 2021 21 of 70 2 to 1 0 AWG 33 6 to 53 5 mm2 2 to 1 0 AWG 33 6 to 53 5 mm2 2 to 1 0 AWG 33 6 to 53 5 mm2 2 to 1 0 AWG 33 6 to 53 5 mm2 ...

Page 22: ...o 53 5 mm2 4 to 1 0 AWG 21 1 to 53 5 mm2 2 to 1 0 AWG 33 6 to 53 5 mm2 Electric Shock Hazard Components with hazardous voltage and energy will electrocute the operator Ensure AC power doesn t flow into inverter Verify with a multimeter Turn the AC Switch OFF before wiring Wire the AC Connections as shown in Figure 3 14 For the AC connections use compression lugs with a single hole for a in or M12 ...

Page 23: ...layer is a poor conductor which could lead to thermal issues production loss or damage to the inverter Clockwise Phase Rotation Ensure the inverter is installed with a clockwise phase rotation A counterclockwise phase rotation will prevent the inverter from running If the inverter reports a PLL Phase Lock Loop error or the frequency voltage measurements seem incorrect check your phase rotation Swa...

Page 24: ...its multiplied by 1 25 must be less than 320 A Equation 3 2 1 5 1 66 2 0 at STC 3 1 1 25 500A 3 2 DC AC Ratio and Isc Requirements Both the DC AC ratio and Isc limit requirements must be met Failure to stay within these limits may result in damage NOT covered under warranty 3 8 2 DC Input Specifications Table 3 5 DC Input Specifications XGI 1500 125 125 XGI 1500 125 150 XGI 1500 150 166 XGI 1500 1...

Page 25: ...or 28 positions 25 A 20 positions 30 A 16 positions Fuse Configuration Both Poles Fused Switch Configuration Both Poles Switched Open Fuse Holders Verify the absence of DC voltage and current when inserting or removing fuses Use Correct Fuses Size the fuses following NEC requirements DC Connection Using the XGI Remote or Attachable Combiner Wire the DC Connections as shown in Figure 3 15 using the...

Page 26: ... mm2 4 0 AWG 107 mm2 250 kcmil 127 mm2 300 kcmil 152 mm2 Maximum Wire Size Aluminum 500 kcmil 240 mm2 500 kcmil 240 mm2 500 kcmil 240 mm2 500 kcmil 240 mm2 For the DC connections use compression lugs with a single hole for a in or M12 stud and sized for the wire gauge used The width of the lugs must be 1 5 in 38 mm or less Torque to 220 in lbs 25 N m using an 18mm socket and torque driver A hex nu...

Page 27: ... Confirm proper polarity of connections with a multimeter The PV Output Circuit Wiring Harness Assembly is designed to simplify the field interconnection of the Combiner and the XGI 1500 inverter The Wiring Harness Assembly comprises A straight section of 2 inch PVC about 7 inches in length with 90 degree elbows and threaded couplings at each end Two 2 4 0 AWG conductors for the PV Output Circuit ...

Page 28: ... the conduit coupling to secure the conduit assembly in place in both enclosures 4 Proceed to terminate the PV Output Circuit conductors to the lugs noting carefully the polarity markings on the terminations and insulation color coding Red POSITIVE Black NEGATIVE 5 For terminations in the inverter wiring section torque the positive and negative terminals to 220 in lbs 25 N m and the ground termina...

Page 29: ...hat will damage critical components IMPORTANT Risk of condensation is greatest when inverters are left inoperative in the time between installation and beginning daily normal operation To manage moisture during this time it may be necessary to use a desiccant package not included The desiccant package should be placed in the Wiring Box in lower right corner near the communication conduit entrance ...

Page 30: ...r back on the inverter Use a 3 Phillips head torque driver to tighten the cover screws to 40 in lbs 4 5 N m Refer to Figure 3 6figure Torque to Specified Value Overtightening the screws may warp the cover or strip the screws When replacing the cover all 10 screws must be installed to maintain the enclosure rating This prevents water from entering the enclosure that could potentially damage the equ...

Page 31: ...duits from underground circuits are appropriately sealed Electrical Check Verify that the AC circuit breaker is appropriately sized Refer to Section 0 Test whether the AC voltage is within 5 of nominal 570V 630V Verify that the AC phase conductors are oriented for clockwise phase rotation Test the polarity of the DC inputs See Sections 3 8 and 3 9 Verify that the DC open circuit voltage of the inp...

Page 32: ...operly configured and compliant with the interconnection agreement Connect a power quality analyzer oscilloscope or other digital voltage measurement device on the inverter side of the PV system disconnect The PV system switch is typically the disconnecting means closest to the point of interconnection The meter is used to verify voltage and timing requirements during plant shutdown Once all inver...

Page 33: ...uctors must utilize Ethernet Cat 6 Shielded cable The shield must be terminated properly to provide connection with ground INFO Ethernet Cat 6 Shielded Cable Solar PV inverters create an electrically noisy environment that can disrupt inverter communication It is important to use Cat 6 Shielded cable to ensure that communication is not interrupted Separate Communication Conductors from Power Condu...

Page 34: ...is 50 inverters When using star or mixed network configurations the maximum number of inverters from one end of a daisy chain to the end of any other daisy chain within a given Cluster must not exceed 50 inverters The maximum number of inverters in any Cluster must not exceed 50 Use shielded Cat6 Ethernet cable ONLY The maximum length between any two devices is 328 ft 100m for all inverter Etherne...

Page 35: ...Installation and Operation Guide SOLECTRIA XGI 1500 Rev E 5 Mar 2021 35 of 70 Figure 5 2 Mixed network ...

Page 36: ...t built in firewall that is automatically established on the Gateway Inverter after receiving an IP address assigned via a DHCP or through manual static IP configuration This act of establishing a firewall also designates an inverter as a Gateway Inverter Once this firewall is established unauthorized inbound or outbound communication is not permitted through the Gateway Inverter Networking with O...

Page 37: ...be employed in order for the third party DAS to reach each inverter as an Endpoint Device 1 Port forwarding 2 Static Routing discussed in detail in Section 5 7 Be sure to consult with the monitoring provider before installation Third Party Data Acquisition System DAS Connection NOTICE Ethernet Only Connection The XGI 1000 series inverter only supports Ethernet connections to a third party DAS Conn...

Page 38: ...ovider before implementing When Port Forwarding is implemented a third party DAS can address each inverter using the Gateway Inverter External IP and the specified port for the inverter with the cluster The Gateway Inverter External IP is assigned to the Gateway Inverter via the DHCP or configured manually using a static IP 5 9 1 Port Forwarding Reserved DHCP IP Address Before configuring Port For...

Page 39: ...xternal device DAS Up to two IP Subnet pairs can be entered on each gateway NOTICE CYBER SECURITY Configuring an entire IP subnet will not only allow the desired DAS device but would also enable all the other devices authorized or unauthorized in the subnet to be able to access the Inverter cluster LAN Use the most restrictive settings possible Figure 5 6 Enabling external Modbus access Port Forwa...

Page 40: ...Endpoint Device by a DAS or other external device using the Inverter Cluster IP address and port 502 for example 10 78 125 31 502 Inverter Cluster IPs can be configured see Section 5 11 5 10 1 Static Routing Configuring the Gateway Inverter To configure Static Routing first Enable External Modbus Access by selecting the check box using the GUI of the desired Gateway Inverter By default the Gateway...

Page 41: ... IP on the Modbus Access Configuration page see Figure 5 8 The method of entering static routing rules varies depending on the device or operating system for more information work with your IT professional Manage Cluster IP Address The internal Cluster IP Address are automatically assigned to each XGI inverter at the factory If desired the IP address can be managed and statically assigned Supporte...

Page 42: ...rts The SOLECTRIA XGI has two interchangeable Ethernet Ports These connections are located in the right hand compartment within the Wire Box 5 12 1 Weather Station Connection Optional Only use weather stations that connect using Ethernet As with all other non inverter Ethernet devices these should be connected outside of the Cluster LANs ...

Page 43: ...er within a given Cluster INFO Inter Inverter Communication Over Ethernet Only All XGI inverters are equipped with a WiFi antenna which is used to tether a smart device to the inverter or Cluster Inverters do not communicate to each other over WiFi all inter inverter communication is over Ethernet only 6 1 2 XGI Gateway Inverter Every XGI Cluster has one and only one XGI Gateway Inverter The Gatew...

Page 44: ... 1 Connecting to the Inverter Ethernet To access the inverter using Ethernet connect an Ethernet cable from the laptop to the inverter The Ethernet port is located inside the wiring box see Figure 3 7 Wait 15 seconds for the laptop to obtain an IP address from the XGI Inverter DHCP must be enabled on the PC connected to the inverter Once the laptop recognizes the Ethernet connection open your pref...

Page 45: ...he XGI provides a strong WiFi signal with 75ft and direct line of site Ensure the WiFi antenna is connected to the inverter Try closing your web browser and re opening a new session Check to make sure the XGI network LED is illuminated The inverter takes approximately 5 minutes to fully boot up if connecting after a recent power cycle wait 5 minutes and try again 6 2 3 Inverter List The Inverter L...

Page 46: ...inverter has an inverter issue and cannot produce power Inverter Warning This indicates that the inverter has an issue but can produce power In the sample inverter list in several nodes are worth noting Inverter 2 1 This inverter indicated in bold is the inverter that the smart device or laptop last accessed and it is operating normally Inverter 2 2 This inverter is the Gateway Inverter denoted wi...

Page 47: ...the inverter status icons will give their current state as shown in Figure 6 3 Current Status with Network and Communication Working and Maintenance with an Event The menu button is located in the upper left corner represented by three horizontal lines When clicked a drop down menu appears In the upper right is a Login Logout button ...

Page 48: ...D CASE SENSITIVE ADMIN SolectriaSolar The inverter will log the user out automatically after it is idle for 30 minutes 6 2 6 Changing Settings Changing settings or configurations in the GUI is easy and intuitive Most pages allow the user to enter text numbers select check boxes or actuate sliders Once a setting or configuration has been adjusted use the Save button to save any changes Many fields ...

Page 49: ... Logs Edit Inverter List Firmware Update First Time Start Wizard AC Voltage and Frequency Trip Settings Power Limiting Power Factor Control Reactive Power Control Volt VAr Volt Watt Freq Watt Ramp Rate Settings Abnormal AC Voltage Detection Abnormal AC Freq Detection Recovery Settings Edit Inverter Name Time and Date Configuration Factory Default Edit Lifetime Energy Restart Inverter Internet Conn...

Page 50: ...r has stabilized but prior to peak production reducing lost revenue Having the Enable Automatic Remote Firmware update unchecked is not recommended as product improvements may have occurred since the purchase of the product If the user disables this feature the site operator will be responsible for performing any firmware updates Manual Firmware Updates Locally Manual firmware updates performed lo...

Page 51: ...Installation and Operation Guide SOLECTRIA XGI 1500 Rev E 5 Mar 2021 51 of 70 Figure 7 1 Firmware Update ...

Page 52: ...ed on for a minimum of 10 minutes Startup Wizard Run the Startup Wizard by logging into one of the inverters and selecting Startup Wizard from the main menu Name the Inverters Enter a name for each inverter on the list Configure the Reference List Add or Remove the inverters from the reference list This list consists of all inverters that are currently communicating in the Cluster AND inverters th...

Page 53: ...ote that some of these events can create a hazardous situation indicated by DO NOT TOUCH in Table 9 1 Critical Event Codes Ground Fault Hazard Inverter enclosure is an electrical hazard DO NOT TOUCH any equipment including but not limited to the inverter the PV array disconnect switch the PV array combiner the PV panels or the PV racking system Immediately contact the installer or another qualifie...

Page 54: ... has been detected Insolation resistance between the DC conductors and ground is below the allowable limit Check the array for an unintentional reference to ground DO NOT TOUCH any equipment including but not limited to the inverter the PV array disconnect switch the PV array combiners the PV panels the PV racking system Immediately contact the installer or another qualified person to locate and r...

Page 55: ... Inspect the AC conductors for damage If AC voltage is present and the inverter will not grid connect contact Technical Support 4 Open Phase Detected Open AC phase condition has been detected Using a CAT III multi meter verify the AC voltage If a phase loss is identified check all AC fuses or breakers Inspect the AC conductors for damage If not phase loss is identified contact Technical Support 5 ...

Page 56: ...Voltage 3 Detected AC low voltage region 3 detected Using a CAT III multi meter verify the AC voltage If there is a discrepancy of greater than 2 between the measured results and the voltage reported by the inverter contact Technical Support otherwise wait for the grid conditions to improve 12 AC High Voltage 1 Detected AC high voltage region 1 detected Using a CAT III multi meter verify the AC vo...

Page 57: ...er network 31 Invalid Configuration Request An external request to adjust setting beyond the allowable limits Check to make sure the value being entered is acceptable and re enter 32 Reserved 9 1 3 Information Events Information events will not cause the inverter to cease producing AC power and are used for reference There is no LED for them Table 9 3 Information Event Codes Info Event Code Displa...

Page 58: ...the wiring portion of the inverter after the inverter has been running for at least an hour Refer to Figure 7 1 1 Allow the inverter to run for at least an hour above 50 power before performing thermography 2 Turn off the inverter first by setting the DC Switch on the inverter to the OFF position then by turning the AC Switch on the inverter to the OFF position 3 Remove the 10 screws securing the ...

Page 59: ...he inverter 9 2 2 Cleaning the Fans and Cooling Plenum The XGI 1500V inverter has three fans on the right hand side of the enclosure These fans are protected with finger guards Over time these guards may collect debris that restricts airflow and reduces the effectiveness of the cooling system Keeping the fans and cooling plenum clean will prevent the inverter from overheating To clean the fans 1 T...

Page 60: ...so collect in the cooling plenum on the heatsinks and inductors located in this section of the inverter A removable panel located at the rear of the inverter provides access for cleaning Figure 9 3 Rear Access Panel Do not use any metallic tools within the cooling plenum as this could damage the insulation on the inductors ...

Page 61: ...rter to the OFF position 2 Remove the 11 screws from the rear access panel and set aside Figure 9 4 Rear Access Panel Removed 3 Use a vacuum with a non metallic nozzle to remove the debris from air plenum heatsink and inductors Use a stiff nylon brush to loosen any stubborn debris 4 Replace the cover before re energizing the inverter Failure to keep the inverter properly maintained may cause perma...

Page 62: ...ack feed 0 A Open Circuit Strike Voltage 920 VDC Synchronization Inrush Current 12 ARMS Output Power Factor Unity 0 99 Adjustable from 0 80 to 0 80 Grid Type 3 Phase Wye with Ground and Neutral Nominal Output Voltage 600 VAC Nominal Frequency 60 Hz Output Voltage Range 12 to 10 Frequency Range 57 62 Hz Max Output Overcurrent Protection 200 A Max Output Fault Current 189 ARMS 10 9ms Max Output Curr...

Page 63: ...ge 1 Clearing Time 0 2 s Clearing Time Adjustable Up to and Including 0 1 s V 45 0 16 s 0 16 s 45 V 60 1 0 s 11 s 60 V 88 2 0 s 21 s 88 V 110 No trip No trip 110 V 120 1 0 s 13 s f 120 0 16 s 0 16 s Table 10 4 Frequency Limits and Trip Times Frequency Range 0 05 Hz Clearing Time 0 2 s Clearing Time Adjustable Up to and Including 0 1 s F 57 Hz 0 16 s 10 s 57 Hz F 59 5 Hz 2 0 s 300 s 59 5 Hz F 60 5 ...

Page 64: ... 5 Normal Temperature Ranges Ambient Temperature Range 40 F to 140 F 40 C to 60 C Derating Temperature 113 F 45 C Storage Temperature Range 40 F to 167 F 40 C to 75 C Figure 10 3 Derating with Temperature 0 10 20 30 40 50 60 70 80 90 100 40 30 20 10 0 10 20 30 40 45 50 55 60 Percent of Power Ambient Temp C of Power vs Ambient Temp 166kW 125kW 150kW ...

Page 65: ...n Guide SOLECTRIA XGI 1500 Rev E 5 Mar 2021 65 of 70 Figure 10 4 Derating with Altitude 0 10 20 30 40 50 60 70 80 90 100 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 Percent of Full Power Altitude km of Rated Full Power vs Altitude ...

Page 66: ...e XGI 1500 inverter This combination is typically used in distributed PV system architecture See Table 11 1 below for the specifications of the CA XGI1500 series combiners Table 11 1 Attachable Combiner Specifications 15A or 20A fuses included 25A 30A 16 20 24 26 28 20 16 Ungrounded PV Source Circuits Only Both Positive and Negative Polarities Fused Enclosure Material Weight and Rating Polyester P...

Page 67: ...Mar 2021 67 of 70 Figure 11 2 SOLECTRIA XGI 1500 with the Attachable Combiner Box Figure 11 3 SOLECTRIA XGI 1500 Attached Combiner Box 10 6 in 260mm 15 in 380mm 29 5 in 750mm UPPER MOUNTING BRACKET LOWER MOUNTING BRACKET FUSE HOLDERS GROUND TERMINAL BUSBARS AND ...

Page 68: ... Aluminum 85 lbs 38 6 kg NEMA Type 4X Height 29 5 in 750 mm Width 18 1 in 460 mm Depth 11 in 280 mm Enclosure Material Weight and Rating Safety Certification Listing Certification Agency Standard Warranty Overall Dimensions UL 1741 Intertek 5 Years Maximum Voltage Fuse Rating Options Fused Positions DC Disconnect Input PV Source Circuit Configuration Fuse Configuration 2 Pole DC Disconnect Integra...

Page 69: ... please visit http solectria com support documentation warranty information grid tied inverter warranty letter Yaskawa Solectria Solar Contact Information Table 12 1 Yaskawa Solectria Solar Contact Information Telephone 978 683 9700 Fax 978 683 9702 Sales Support inverters solectria com Customer Support 978 683 9700 x2 Website www solectria com ...

Page 70: ...Installation and Operation Guide SOLECTRIA XGI 1500 Rev E 5 Mar 2021 70 of 70 Authorization to Mark ...

Reviews: