10 Troubleshooting
YASKAWA
SIEP YEACOM 06 V1000 Option PROFINET SI-EP3/V Technical Manual
50
Option Fault Monitors U6-98 and U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in
Table 30 Option Fault Monitor Descriptions
Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option SI-EP3/V status. U6-99 is cleared upon a network-issued fault reset and upon power-
up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.
Fault Condition
Fault Declared
Status Value
(U6-98/U6-99)
Description
No Fault
n/a
0
No faults.
Force Fault
EF0
3
Network sent a message to force this node to the fault state.
Network Link Down
BUS ERROR
1300
No network link to option board.
Network Failure
BUS ERROR
1301
Connection with PLC Timeout.
Default MAC Address
None
1303
Factory default MAC Address programmed into the option. Return for
reprogramming.
No IP Address
None
1304
No IP Address has been programmed into the option.
No Station Name
None
1305
No Station Name has been programmed into the option.
Config Error
None
1306
Configuration error on power-up.
Init. Failure
None
1307
Initialize error on power-up.
Permanent
Communication Loss
BUS ERROR
1308
Fatal error in MAC/PHY hardware, requires power cycle to recover.