5 Operation
5.4.1 Basic Settings for Position Control
5-38
(3) Connection Example
The following diagram shows a connection example. Use an SN75ALS174 or MC3487 manufactured by
Texas Instruments Inc., or equivalent for the line driver.
Line Driver Output
represents twisted-pair wires.
Open-collector Output
Set limit resistor R so the input current, i, falls between 7 mA to 15 mA.
represents twisted-pair wires.
Line driver
SERVOPACK
Host controller
CN1
7
8
14
15
12
11
PULS
SIGN
CLR
/PULS
SIGN
/SIGN
CLR
/CLR
PULS
Reverse
Phase A
Forward
Phase B
∗
150
Ω
4.7 k
Ω
Photocoupler
150
Ω
4.7 k
Ω
Photocoupler
150
Ω
4.7 k
Ω
Photocoupler
FG
FG
47
• Use a shielded cable for I/O signals and ground both ends of the shield.
• Connect the shield of the cable on the SERVOPACK side to the connector shell so
that the shield will be connected to the frame ground (FG) through the connector.
CN1
7
8
14
15
12
11
/PULS
SIGN
/SIGN
CLR
/CLR
PULS
∗
150
Ω
4.7 k
Ω
4.7 k
Ω
4.7 k
Ω
150
Ω
150
Ω
FG FG
Vcc
Vcc
Vcc
Tr
Tr
Tr
R
R
i
i
i
R
SERVOPACK
Host controller
Example
When Vcc is +12 V: R = 1 k
Ω
When Vcc is +24 V: R = 2.2 k
Ω
When Vcc is +5 V: R = 180
Ω
Note: In case of open-collector outputs,
the signal logic is as follows.
When Tr is ON
High level input or
equivalent
Low level input or
equivalent
When Tr is OFF
Photocoupler
Photocoupler
Photocoupler
Analog
Summary of Contents for SGDV SERVOPACK
Page 23: ...www dadehpardazan ir 88594014 15 xxii ...
Page 53: ...www dadehpardazan ir 88594014 15 2 Panel Operator 2 10 ...
Page 203: ...www dadehpardazan ir 88594014 15 5 Operation 5 11 5 Precautions for Safety Functions 5 86 ...
Page 275: ...www dadehpardazan ir 88594014 15 6 Adjustments 6 9 7 Position Integral 6 72 ...