4.3 Table Parameter Settings for Speed/Torque (Pressure) Table Operation
4.3.2 Settings for Speed Table Operation
4-5
4
Speed/T
or
que (Pr
essur
e) T
able Operation
4.3.2
Settings for Speed Table Operation
Set the ten speeds for speed table operation in Pn6AC to Pn6BE and the speed table switch-
ing positions for the ten speeds for speed table operation in Pn6C0 to Pn6D0.
Pn6A4
n.
3
Use torque (pressure) table reference 1
(Pn6D2) through torque (pressure) table refer-
ence 3 (Pn6D6) for torque (pressure) table
operation.
Immediately
Setup
n.
4
Use torque (pressure) table reference 1
(Pn6D2) through torque (pressure) table refer-
ence 4 (Pn6D8) for torque (pressure) table
operation.
n.
5
Use torque (pressure) table reference 1
(Pn6D2) through torque (pressure) table refer-
ence 5 (Pn6DA) for torque (pressure) table
operation.
Continued from previous page.
Parameter
Meaning
When Enabled
Classification
Pn6AC
Speed Table Reference 1
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to
2,147,483,647
1 reference unit/s
0
Immediately
Setup
Pn6AE
Speed Table Reference 2
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to
2,147,483,647
1 reference unit/s
0
Immediately
Setup
Pn6B0
Speed Table Reference 3
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to
2,147,483,647
1 reference unit/s
0
Immediately
Setup
Pn6B2
Speed Table Reference 4
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to
2,147,483,647
1 reference unit/s
0
Immediately
Setup
Pn6B4
Speed Table Reference 5
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to
2,147,483,647
1 reference unit/s
0
Immediately
Setup
Pn6B6
Speed Table Reference 6
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to
2,147,483,647
1 reference unit/s
0
Immediately
Setup
Pn6B8
Speed Table Reference 7
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to
2,147,483,647
1 reference unit/s
0
Immediately
Setup
Pn6BA
Speed Table Reference 8
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to
2,147,483,647
1 reference unit/s
0
Immediately
Setup
Pn6BC
Speed Table Reference 9
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to
2,147,483,647
1 reference unit/s
0
Immediately
Setup
Continued on next page.
Speed
Speed
Speed
Speed
Speed
Speed
Speed
Speed
Speed