Step

5

Changing Parameters and  

Monitoring the V1000 

This step shows how to access and modify a V1000 parameter as 
well as how to monitor V1000 signals such as output frequency 
and motor current.

Make sure all protective covers have been re-attached and power 
is turned on.  

DO NOT RUN THE MOTOR. 

Press

two times until 

.

the digital operator shows the parameter

menu (PAr) then press

V1000 Digital Operator power-up state

Press              to select the digit

you would like to change. Next use

          and             to select the 

parameter group, sub-group or number.

Modify the parameter value using 

            and             and press 

                to save the new value.

Access Parameter Menu and Change Parameter Value

Monitor Motor Frequency and Motor Current

Press            until the 

FOUT

 

LED turns on. The display now shows 

the actual drive output frequency in Hz. 

Pressing              again will 

show the motor output current. The ‘A’ 

behind the value means ‘Amps’.

Please refer to the technical manual 
on how to access other drive 
monitors.

V1000 Digital Operator power-up state

Motor Current

Output Frequency

Change Parameter Value

Select Parameter

Select Parameter Menu

This step shows how to setup up the sequence and reference method of the V1000. The sequence 
method determines how the V1000 drive receives its start and stop command and the reference 
method determines how the speed of the motor is controlled. Make sure all protective covers have 
been re-attached and power is turned on.  

DO NOT RUN THE MOTOR. 

This section may require you to change one or more V1000 parameters. Please refer to Step 5 for a 
detailed explanation on how to change parameters.

SELECT START / STOP CONTROL METHOD

1.

 

Start / Stop Control from Digital Operator

Go to parameter b1-02,                                      

Set Value to

b1-02

2.

 

Start / Stop Control from external terminals (switch or relay contact)

Go to parameter b1-02,                                      

Set Value to

( Factory Default)

S3

S5 S6 S7 HC SC H1 RP

S2

S4

S1

P1 P2 PC A1 A2 +V AC AM AC MP

Wiring Diagram: 2-Wire Control

Forward

Reverse

S3

S5 S6 S7 HC SC H1 RP

S2

S4

S1

Wiring Diagram: 3-Wire Control

Start

Switch

Reverse

Stop 

Switch

Normally 

Open

Normally 

Closed

Use for momentary contacts

Use for maintained contacts

NOTE: It is beyond the scope of this document to program the V1000 drive for network communication control. Please refer to the programming 
manual for this selection.  

SELECT SPEED METHOD

b1-01

(Factory Default)

1.

 

Adjust motor speed / frequency from the Digital Operator

Go to parameter b1-01,                                      

Set Value to

2.

 

Start / Stop Control from external terminals (switch or relay contact)

Go to parameter b1-01,                                      

Set Value to

(Factory Default)

Potentiometer

2K Ohm

P1 P2 PC A1 A2 +V AC AM AC MP

0 ~ 10Vdc

 

4 ~ 20mA

+

Located inside the drive on 

the control card

To adjust frequency use              /              and press               .

User Terminals

User Terminals

User Terminals

User Terminals

(Set Parameter A1-03 to 3330)

Step

6

Selecting Start/Stop and Speed Method 

The following table lists the general purpose application parameters as well as frequently asked questions.

This section may require you to change one or more V1000 parameters. Please refer to Step 5 for a detailed 
explanation on how to change parameters.

FREQUENTLY ASKED QUESTIONS

GENERAL PURPOSE APPLICATION PARAMETERS

Question: How do I reset the drive back to factory default settings?

Answer:    Go to parameter A1-03 and set value 2220 for 2 wire control or 3330 for 3 wire control
                  (Please refer to Step 6 for wiring diagram)

Question:  How do I adjust the time it takes the motor to speed up or slow down?

Answer:    Adjust the acceleration time parameter C1-01 and deceleration time C1-02.

Question: How do I prevent my drive from tripping on an 

OV 

fault (overvoltage) while my motor is ramping down?

Answer:    Increase deceleration time parameter C1-02.

Question: How do I prevent my drive from tripping on an 

OL1 

fault (overload) while my motor is ramping down?

Answer:    Verify motor rated current parameter E2-01 and motor overload parameter settings
                  L1-01 Motor overload selection, L1-02 Motor overload protection time.
               
Question: I want to run my motor above the nominal motor speed?

Answer:    Increase the value of parameter E1-04 Maximum Frequency 

                  Warning! Verify that the motor and system allow for this.

Yaskawa Electric America, Inc.

2121 Norman Drive South 

Waukegan, IL 60085 

(800) YASKAWA (927-5292)     Fax (847) 887-7310

[email protected]    www.yaskawa.com

YEA Document Number: TM.V1000.01  5/15/2008  © Yaskawa Electric America, Inc.

Step

7

Quick Start Parameters 

 

Parameter

 

 

Default Value

 

 

Description

 

 

Comments

 

 b1-01

 

1

 

Reference Source 
Speed Control Method

 

0 = Digital Operator (Adjust Motor Speed from keypad) 
1 = Terminals (Speed Pot. / 0 – 10V / 4—20mA)

 

b1-02

 

1

 

Run Source /  
Start/Stop Control Method

 

0 = Digital Operator (Start/Stop motor from keypad) 
1 = Terminals (Start/Stop using external contact / switch)

 

b1-03

 

1

 

Stop Method Selection 

 

0 = Ramp to stop (Motor ramps down at stop command) 
1 = Coast to stop (Motor freewheels at stop command)

 

b1-04

 

0

 

Reverse Operation

 

0 = Allow motor to run in reverse direction 
1 = Reverse direction prohibited 

 

C1-01

 

10.0 sec.

 

Acceleration Time

 

The time it takes to ramp up from 0 to maximum motor speed.

 

C1-02

 

10.0 sec.

 

Deceleration Time

 

The time it takes to ramp down from maximum motor speed to 0.

 

C6-01

 

1

 

Normal / Heavy Duty

 

0 = Normal Duty (Use for fan and pump applications) 
1 = Heavy Duty (Use for conveyor, mixer, applications)

 

d1-01

 

0.00 Hz

 

Frequency Reference

 

 Frequency setting when speed is set from the keypad.

 

d2-01

 

100.0 %

 

Frequency Upper Limit

 

 Maximum motor speed allowed (e.g. 100 % = Max rpm)

 

d2-02

 

0.0 %

 

Frequency Lower Limit

 

 Minimum motor speed allowed (e.g. 100 % = Max rpm)

 

E2-01

 

*

 

Motor Rated Current

 

 Motor nameplate current

 

L1-01

 

1

 

Motor Overload Selection

 

0 = Disabled 
1 = Standard Fan Cooled Motor 
2 = Standard Blower Cooled Motor 
3 = Vector Duty Motor 

 

L1-02

 

1.0 min

 

Motor Overload Time

 

Sets the motor thermal overload protection time.

 

 

V1000 CHEAT SHEET 

Page 2 of 2 