9
For YASKAWA’s inverter motor with PG, PG is installed at the opposite drive
end. Then, phase A lags phase B by a phase angle of 90
_
at motor forward run.
(Motor runs CCW as viewed from PG.) Therefore, when using this motor or
similar motors, connect phases A and B to the option card after replacing phase
output. The pulse monitor on this option shows phase A leading phase B by a
phase angle of 90
_
.
Make sure the followings when wiring.
S
To prevent noise, use shielded wire and separate from heavy current circuits
(200VAC or greater) or relay drive circuits. (Wire length to the PG connec-
tor must be 50m or shorter.)
S
Connect both ends of the unused wire of the shielded wire to the 0V termi-
nal.
S
Connect the grounding lead wire (E) to pin 12 of the control board of the
inverter.
S
Applicable wire sizes for terminal block TA1 and TA2 are shown below.
[Terminal: MKDS1 series manufactured by Phoenix Contact GmbH &
Co.]
[mm
2
]
AWG
I [A]
VAC [V]
Thin twisted wire
1
16
12
125
Solid wire
1.5
16
12
125
UL
22
−
16
10
300
CSA
28
−
16
10
300
CSA
28
−
16
10
150
Terminal block TA1,TA2 side
Connecting wire end
5.5 mm
Notes on selecting cables
Too thick a cable applies pressure to the option card and may lead to failure.
Too thin a cable may lead to imperfect contact or a break in the wire.
NOTE