Register No.
Contents
00E5H
oFC3x Contents (CN5-C)
bit 0
Comm. ID Error (oFC30)
bit 1
Model Code Error (oFC31)
bit 2
Sumcheck Error (oFC32)
bit 3
Comm. option timeout waiting for response (oFC33)
bit 4
MEMOBUS Timeout (oFC34)
bit 5
Drive timeout waiting for response (oFC35)
bit 6
CI Check Error (oFC36)
bit 7
Drive timeout waiting for response (oFC37)
bit 8
Control Command Selection Error (oFC38)
bit 9
Drive timeout waiting for response (oFC39)
bit A
Control Response Selection 1 Error (oFC40)
bit B
Drive timeout waiting for response (oFC41)
bit C
Control Response Selection 2 Error (oFC42)
bit D
Control Response Selection Error (oFC43)
bit E, F
Reserved
00E6H to 00FFH
Reserved
<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive is set for
Refer to Power Ratings on page 394
<3> Communication error contents are saved until the fault is reset.
<4> Set the number of motor poles to parameter E2-04.
u
Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
Register No.
Contents
0001H
Digital Input Command
bit 0
Forward Run (0: Stop 1: Run)
bit 1
Direction Command (0: Forward, 1: Reverse)
bit 2, 3
Reserved
bit 4
External Fault
bit 5
Fault Reset
bit 6 to B
Reserved
bit C
Multi-Function Digital Input S5
bit D
Multi-Function Digital Input S6
bit E
Multi-Function Digital Input S7
bit F
Multi-Function Digital Input S8
0002H
Frequency Reference
30000/100%
C.9 MEMOBUS/Modbus Data Table
532