No.
Name
Setting Range
Default
b5-95
EZ Wake-up Mode
0
update the value of this parameter.
Setting 0: Absolute
Setting 1: Setpoint Data
n
b5-96: EZ Wake-up Time
The drive will wake up when the PID Feedback drops below the b5–94, EZ Wake-up Level for the time set in this parameter.
No.
Name
Setting Range
Default
b5-96
EZ Wake-up Time
1.0 s
update the value of this parameter.
n
b5-34: PID Output Lower Limit
Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower limit
is disabled when set to 0.00%
No.
Name
Setting Range
Default
b5-34
PID Output Lower Limit
-100.0 to 100.0%
0.00%
n
b5-35: PID Input Limit
Sets the maximum allowed PID input as a percentage of the maximum output frequency (E1-04). Parameter b5-35 acts as a
bipolar limit.
No.
Name
Setting Range
Default
b5-35
PID Input Limit
0.0 to 1000.0%
1000.0%
n
b5-40: Frequency Reference Monitor Content During PID
Sets the content of the frequency reference monitor display (U1-01) when PID control is active.
No.
Name
Setting Range
Default
b5-40
Frequency Reference Monitor Content During PID
0, 1
0
Setting 0: Frequency Reference after PID
Monitor U1-01 displays the frequency reference increased or reduced for the PID output.
Setting 1: Frequency Reference
Monitor U1-01 displays the frequency reference value.
n
b5-41: PI Unit Selection
Sets the display units in U5-14 and U5-15.
No.
Name
Setting Range
Default
b5-41
PI Output 2 Unit Selection
0 to 15; 25
0
5.2 b: Application
172