A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
373
Para
me
te
r Lis
t
A
U5: Application Monitor
Use U5 parameters to view application-specific settings.
U5-01 PID Feedback
Displays the PID feedback value in.
10V: 100%
(max. freq.)
0.01
%
A A A
57
U5-02 PID Input
Displays the amount of PID input (deviation
between PID target and feedback).
0.01
%
A A A
63
U5-03 PID Output
Displays PID control output.
0.01
%
A A A
64
U5-04 PID Setpoint
Displays the PID setpoint.
0.01
%
A A A
65
U5-05
PID Differential
Feedback
Displays the 2nd PID feedback value if
differential feedback is used.
0.01
%
A A A
7D2
U5-06
PID Adjusted
Feedback
Displays the subtraction value of both
feedback values if differential feedback is
used.
0.01
%
A A A
7D3
U6: Application Monitor
Use U6 parameters to display drive control information.
U6-01
Motor Secondary
Current (Iq)
Displays the value of the motor secondary
current (Iq).
10 V: 100% 0.1% A A A
51
U6-02
Motor Excitation
Current (ld)
Displays the value calculated for the motor
excitation current (Id).
10 V: 100% 0.1%
−
A A
52
U6-03
ASR Input
Displays the ASR input value if V/f Control
with Simple PG Feedback is enabled.
10V: 100%
(max. freq.)
0.1% A
− −
54
U6-04 ASR Output
Displays the ASR output value if V/f Control
with Simple PG Feedback is enabled.
10V: 100%
(max. freq.)
0.1% A
− −
55
U6-05
Output voltage
reference (Vq)
Output voltage reference (Vq). (q-axis)
10 V: 200 V
(400 V)
0.1
Vac
−
A A
59
U6-06
Output Voltage
Reference (Vd)
Output voltage reference (Vd). (d-axis)
10 V: 200 V
(400 V)
0.1
Vac
−
A A
5A
U6-07 q-axis ACR Output
Displays the current control (ACR) output of
for the motor secondary current (Iq).
10 V: 100% 0.1%
−
A
−
5F
U6-08 d-Axis ACR Output
Displays the current control (ACR) output of
for the motor excitation current (Id).
10 V: 100% 0.1%
−
A
−
60
U6-20
Frequency Reference
Bias (Up/Down 2)
Displays the bias value used to adjust the
frequency reference.
10 V: max.
frequency
0.1% A A A
7D4
U6-21 Offset Frequency
Displays the frequency added to the main
frequency reference.
10 V: max.
frequency
0.1% A A A
7D5
No.
Name
Description
Analog
Output Level
Unit
Control
Mode Addr.
Hex
V/f
O
LV
P
M
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...