A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
351
Para
me
te
r Lis
t
A
L8-03
Overheat Pre-Alarm
Operation Selection
Sets the drive operation when an overheat alarm
OH is detected.
0: Ramp to Stop using the active decel time.
1: Coast to Stop.
2: Fast-stop using the time set in C1-09.
3: Alarm Only. Drive continues running, but
displays an alarm.
4: Reduced Speed Operation. Drive continues
to run with reduced frequency reference as
specified in L8-19.
Settings 0 through 2 trigger a fault relay if the
heatsink becomes too hot.
0 to 4
3
A A A 4AF
L8-05
Input Phase Loss
Protection Selection
Selects the detection of input current phase loss,
power supply voltage imbalance, or main
circuit electrolytic capacitor deterioration.
0: Disabled
1: Enabled
0,1
1
A A A
4B1
L8-07
Output Phase Loss
Protection
Selects the output phase loss detection.
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
Output phase loss is detected when operating
with less than 5% of the drive rated current.
Detection can mistakenly occur if the motor is
too small relative to the drive capacity rating
(this parameter should be disabled in such
cases).
0 to 2
1
A A A
4B3
L8-09
Output Ground Fault
Detection Selection
Selects the output ground fault detection.
0: Disabled
1: Enabled
0, 1
A A A
4B5
L8-10
Heatsink Cooling Fan
Operation Selection
Controls the heatsink cooling fan operation.
0: Fan On-Run Mode - Fan will operate only
when the drive is running and for L8-11
seconds after stop.
1: Fan always on - Cooling fan operates
whenever the drive is powered up.
0, 1
0
A A A
4B6
L8-11
Heatsink Cooling Fan
Operation Delay Time
This parameter sets the delay time for the
cooling fan to shut off after the run command is
removed when L8-10 = 0.
0 to 300 60 s A A A
4B7
L8-12
Ambient Temperature
Setting
Used to input the ambient temperature. This
value adjusts the drives OL2 detection level.
-10 to 5040
°
C A A A
4B8
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...