A.2 Parameter Table
Para
me
te
r Lis
t
A
A.2
Parameter Table
◆
A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the
parameter Access Level, Motor Control Method, Password, User Parameters and more.
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
A1: Initialization Parameters
Use A1 parameters to configure the basic environment for drive operation.
A1-01
Access Level
Selection
Selects which parameters are accessible via the
digital operator.
0: Operation only
1: User Parameters (access to a set of parameters
selected by the user)
2: Advanced Access Level
0 to 2
2
A A A 101H
A1-02
Control Method
Selection
Selects the Control Method of the drive.
0: V/f Control without PG
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
Note: Does not return to the default setting when the
drive is initialized.
0, 2, 5
0
S S S
102
A1-03
Initialize
Parameters
Resets all parameters to factory default settings.
(Initializes the drive then returns A1-03 to 0)
0: No Initialize
1110: User Initialize
(First set user parameter values must be stored using
parameter o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
5550: OPE04 Error Reset
0 to
3330
0
A A A
103
The following parameters are not
reset when the performing
initialization:
A1-00, A1-02, A1-07, and all U2
and U3 monitors.
A1-04 Password 1
When the value set into A1-04 does not match the
value set into A1-05, parameters A1-01 thru A1-03,
A1-06, and A2-01 thru A2-32 cannot be changed.
0 to
9999
0
A A A
104
A1-05 Password 2
0 to
9999
0
A A A
105
This parameter is hidden from
view. To access A1-05, first
display A1-04. Then press the
STOP key while holding down
the up arrow key. Parameter
A1-05 will appear.