2.1 MP3200 Installation
2.1.1 Screw Mounting
2-2
2.1
MP3200 Installation
You can use either of the following methods to install an MP3200.
•
Screw mounting
•
DIN rail mounting
Refer to the following appendix for more information on the installation and application require-
ments.
A.1 MP3200 Installation and Usage Conditions
2.1.1
Screw Mounting
Use the JEPMC-OP3001-E Screw Mounting Attachment to install the Machine Controller.
The installation procedure depends on whether you use a Sub-CPU Module on the Main Rack.
Refer to the following sections.
Using a Sub-CPU Module on the Main Rack (page 2-2)
Not Using a Sub-CPU Module on the Main Rack (page 2-5)
Using a Sub-CPU Module on the Main Rack
Selecting Rack Support Brackets
The Rack Support Bracket depends on the Units that you connect on the left and right sides.
The Screw Mounting Attachment is included with the Power Supply Unit. It can be purchased
separately.
Precaution for Using a Sub-CPU Module on the Main Rack
If you mount the MP3200 with screws, attach a Rack Support Bracket (JEPMC-OP3006-E or
JEPMC-OP3007).
Units Connected on
Right or Left Side
Rack Support
Bracket Model
Locations Supported by Rack Support Bracket
•
CPU-201
•
CPU-202
•
YVD-001
JEPMC-OP3007
Any other Unit
JEPMC-OP3006-E
Note
Important
CPU-201/
CPU202
Attach the JEPMC-OP3007-E.
Unit
connected
on left side
CPU-201/
CPU202 or
YVD-001
Unit
connected
on right side
CPU-201/
CPU202
Attach the JEPMC-OP3006-E.
Unit
connected
on left side
Unit
connected
on right side