MotionSuite™ MP940 Machine Controller Hardware Manual
Section 3: DIP Switch Definition
15
Section 3: DIP Switch Definition
The function of the six switches is explained in the table below.
DIP Switch Settings
Number
Name
Setting
Function
Default
Setting
6
RUN
ON
Application program runs at power ON
ON
OFF
Application program does not run at power ON
5
INIT
ON
When DIP switch 4 is OFF:
Data is copied from flash memory to RAM at power ON.
When DIP switch 4 is ON:
Memory is cleared.
OFF
OFF
When DIP switch 4 is OFF:
Data is not copied from flash memory to RAM at power ON.
When DIP switch 4 is ON:
Nothing
4
TEST
ON
Terminal Mode/Initialization Mode
OFF
OFF
Online
3
FLASH
ON
Program is copied from flash memory to RAM at power ON.
OFF
OFF
Program is not copied from flash memory to RAM at power ON
2
Programming
Port Default
ON
Defaults to Port 1 only
OFF
OFF
The programming port is set up through software selection
1
COPY
ON
Global variables are copied from flash at power ON
OFF
OFF
Global variables are not copied from flash at power ON.
Figure 3.1: MP940 DIP Switches
NO
1
2
3
4
5
6
←
RUN
INITIAL
TEST
FLASH
P.P
COPY
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com