31
6 Related Drive Parameters
6
Related Drive Parameters
The parameters in
set the drive for operation with the option. Confirm proper setting
of all parameters in
before starting network communications. Refer to the manual
packaged with the drive for details on setting parameters.
Table 8 Related Parameter Settings
No.
(Addr.
Hex)
Name
Description
Values
b1-01
(180)
Reference 1 Source
Selects the input method for frequency reference.
0: Keypad
1: Analog Input
2: Memobus/Modbus Communications
3: Option PCB
4: Pulse Train Input
Default: 1
Range: 0 to 4
(Set to 3)
b1-02
(181)
Run Command 1 Source
Selects the input method for the Run command.
0: Keypad
1: Digital Input
2: Memobus/Modbus Communications
3: Option PCB
Default: 1
Range: 0 to 3
(Set to 3)
d5-01
(29A)
Torque Control Selection
0: Speed Control
1: Torque Control
Default: 0
Range: 0, 1
F6-01
(3A2)
Communication Error
Selection
Selects drive response when a bUS error is detected
during communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast Stop (Use C1-09)
3: Alarm Only
Default: 1
Range: 0 to 3
F6-02
(3A3)
Comm External Fault
(EF0) Detect
Selects the condition for external fault detection (EF0).
0: Always detected
1: Detection during run only
Default: 0
Range: 0, 1
F6-03
(3A4)
Comm External Fault
(EF0) Select
Selects drive response for external fault input (EF0)
detection during option communications.
0: Ramp to Stop
1: Coast to Stop
2: Fast Stop (Use C1-09)
3: Alarm Only
Default: 1
Range: 0 to 3
F6-07
(3A8)
MultiStep Ref Priority
Select
0: MultiStep References Disabled
1: MultiStep References Enabled
Default: 1
Range: 0, 1
GEM_M-III_IM_E_conditional.fm 31 ページ 2017年7月7日 金曜日 午後5時9分