6 MECHATROLINK Option Drive Parameters
6
MECHATROLINK Option Drive Parameters
set the drive for operation with the option. Confirm proper setting
of all parameters in
before starting network communications. Refer to the manual
packaged with the drive for details on setting parameters.
Note:
Hex.: MEMOBUS addresses that you can use to change parameters over network
communication are represented in hexadecimal numbers.
Table 6 Parameter Settings
INV: Drive Parameter, CNV: Energy-Saving Unit Parameter
No.
(Hex.)
INV CNV
Name
Description
Values
b1-01
(0180)
–
Reference 1 Source
Selects the input method for frequency reference.
0: Keypad
1: Analog Input
2: Memobus/Modbus Communications
3: Option PCB
4: Pulse Train Input
Default: 1
Range: 0 to 4
b1-02
(0181)
Run Command 1
Source
Selects the input method for the Run command.
0: Keypad
1: Digital Input
2: Memobus/Modbus Communications
3: Option PCB
Default: 1
Range: 0 to 3
b1-18
(0179)
–
Voltage Reference
Source
Selects the voltage reference input source
0: Digital Operator - RUN and STOP keys
1: Control circuit terminals (analog input)
2: MEMOBUS/Modbus communications
3: Option PCB
7: Input voltage based control 1
8: Input voltage based control 2
Default: 8
Range:
0 to 3, 7, 8
F6-01
(03A2)
Communications
Error Selection
Selects drive response when a bUS error is
detected during communications with the option.
When installed to drives:
0: Ramp to stop.
1: Coast to stop.
2: Fast Stop (Use C1-09)
3: Alarm only.
4: Alarm - Run at d1-04
5: Alarm - Ramp to Stop
Default: 1
Range: 0 to 5
When installed to energy-saving units:
1: Stop
3: Alarm Only
Default: 1
Range: 1, 3
F6-02
(03A3)
Comm External Fault
(EF0) Detect
Selects the condition for external fault detection
(EF0).
0: Always detected.
1: Detection during run only.
Default: 0
Range: 0, 1