119
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
5.5 E: Motor Parameters
5.5
E: Motor Parameters
E parameters cover V/f pattern and motor data settings.
u
E1: V/f Pattern
n
E1-01: Input Voltage Setting
Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the
nominal voltage of the AC power supply.
NOTICE: Set parameter E1-01 to match the input voltage of the drive. The drive input voltage (not motor voltage) must be set in E1-01
for the protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.
E1-01 Related Values
The input voltage setting determines the overvoltage and undervoltage detection levels.
Note:
The braking transistor operation levels are valid for the internal braking transistor of the drive. When using an external CDBR
braking chopper, refer to the instruction manual of that unit.
n
V/f Pattern Settings E1-04 to E1-13
illustrates the V/f pattern setting.
NOTICE: The motor may require more acceleration torque with drive operation than with a commercial power supply. Set a proper V/f
pattern by checking the load torque characteristics of the elevator to be used with the motor.
No.
<1> Values shown here are specific to 200 V class drives; double the values for 400 V class drives.
Parameter Name
Setting Range
Default
E1-01
Input Voltage Setting
155 to 255 V
200 V
Voltage
Setting Value of
E1-01
(Approximate Values)
ov Detection Level
Braking Transistor
Operation Level
Uv Detection Level
(L2-05)
200 V Class
All settings
410 V
394 V
190 V
400 V Class
setting
≥
400 V
820 V
788 V
380 V
setting < 400 V
820 V
788 V
350 V
No.
<1> Default setting is determined by the control mode (A1-02).
<2> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
<4> Default setting is determined by the drive model (o2-04).
<5> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<6> Auto-Tuning will set E1-13 to the same value as E1-05.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
10.0 to 120.0 Hz
E1-05
Maximum Voltage
0.0 to 255.0 V
190.0 V
E1-06
Base Frequency
0.0 to 120.0 Hz
E1-07
Middle Output Frequency
0.0 to 120.0 Hz
E1-08
Middle Output Frequency Voltage
0.0 to 255.0 V
E1-09
Minimum Output Frequency
0.0 to 120.0 Hz
E1-10
Minimum Output Frequency Voltage
0.0 to 255.0 V
E1-11
Middle Output Frequency 2
0.0 to 120.0 Hz
0.0 Hz
E1-12
Middle Output Frequency Voltage 2
0.0 to 255.0 V
0.0 V
E1-13
Base Voltage
0.0 to 255.0 V
0.0 V
Summary of Contents for Lift Inverter L1000V
Page 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...