12.6 H: Terminal Function Selection
324
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
■
H5-10: Modbus Register 0025H Unit Sel
No.
(Hex.)
Name
Description
Default
(Range)
H5-10
(0436)
Modbus Register 0025H
Unit Sel
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor register
0025H (output voltage reference monitor).
0
(0, 1)
0 : 0.1 V units
1 : 1 V units
■
H5-11: Comm ENTER Command Mode
No.
(Hex.)
Name
Description
Default
(Range)
H5-11
(043C)
RUN
Comm ENTER Command
Mode
Sets the function to make the Enter command necessary to change parameters through
MEMOBUS/Modbus communications.
0
(0, 1)
0 : ENTER Command Required
Make all parameter changes then input the Enter command. You must use the Enter command to enable changes
to parameters.
1 : ENTER Command Not Required
It is not necessary to input the Enter command to change parameters.
■
H5-12: Run Command Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-12
(043D)
Run Command Method
Selection
Sets the input method for the Run command when
b1-02 = 2 [Run Command Selection 1 =
Memobus/Modbus Communications]
or
b1-16 = 2 [Run Command Selection 2 = Memobus/
Modbus Communications]
.
0
(0, 1)
0 : FWD/Stop, REV/Stop
The drive uses bit 0 in command data 0001H of the MEMOBUS register in the motor forward Run command (bit
0 = 1) and the stop command (bit 0 = 0). The drive uses bit 1 in the motor reverse Run command (bit 1 = 1) and
the stop command (bit 1 = 0).
1 : Run/Stop, FWD/REV
The drive uses bit 0 in command data 0001H of the MEMOBUS register in the motor Run command (bit 0 = 1)
and the stop command (bit 0 = 0). The drive uses bit 1 in the direction of motor rotation command (Forward run
(bit1 = 0) or Reverse run (bit 1 = 1)).
■
H5-17: ENTER command response @CPU BUSY
No.
(Hex.)
Name
Description
Default
(Range)
H5-17
(11A1)
Expert
ENTER command response
@CPU BUSY
Sets operation when the EEPROM write command is sent without EEPROM write available.
Usually it is not necessary to change this setting.
0
(0, 1)
0 : Ignore Command(No ROM/RAM Write)
1 : Write to RAM Only
■
H5-18: Motor Speed Filter over Comms
No.
(Hex.)
Name
Description
Default
(Range)
H5-18
(11A2)
Motor Speed Filter over
Comms
Sets the filter time constant used when monitoring motor speed during MEMOBUS/Modbus
communications or with a communication option.
0 ms
(0 - 100 ms)
Sets the filter time constant when you monitor the output frequency or motor speed during MEMOBUS/Modbus
communications or use of the communication option.
These are the MEMOBUS registers:
•
003EH (Output Frequency)
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Summary of Contents for LA500
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Page 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...