3.8 Control Circuit Wiring
■ Output Terminals
Table 3.6
lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
output.
Note: M ulti-function relay output terminals are rated at a minimum o f 10 mA. I f less than 10 mA is required, use the photocoupler
outputs (P1-C1, P2-C2). Using the wrong current output level may cause the output to malfunction when the terminal is activated.
Table 3.6 Control Circuit Output Terminals
Type
No.
Terminal Name (Function)
Function (Signal Level) Default Setting
Page
Fault Relay
MA
N.O.
30 Vdc, 10 m A to 1 A; 250 Vac, 10 m A to 1 A
Minimum load: 5 Vdc, 10 mA
175
MB
N.C. output
MC
Fault output common
Multi-Function
Relay Output
M1
M ulti-function relay output 1 (Brake release command)
Contact relay output
30 Vdc, 10 m A to 1 A
250 Vac, 10 m A to 1 A
Minimum load: 5 Vdc, 10 mA
175
M2
M3
M ulti-function relay output 2 (Output contactor close command)
M 4
M5
M ulti-function relay output 3 (Drive ready)
M6
Multi-Function
Photocoupler
Output
P1
Photocoupler output 1 (During Frequency output)
48 Vdc, 2 to 50 mA
-
C1
-
P2
Photocoupler output 2 (Not Used/Through M ode)
-
C2
-
Monitor Output
FM
A nalog monitor output 1 (Output speed)
-10 to +10 Vdc or 0 to +10 Vdc
1 86
AM
Analog monitor output 2 (Output current)
AC
Monitor common
0 V
-
Safety Monitor
Output
D M +
Safety monitor output
Outputs status o f Safe D isable function. Closed when both Safe Disable
channels are closed. Up to +48 Vdc 50 m A
-
DM-
Safety monitor output common
■ Serial Communication Terminals
Table 3.7 Control Circuit Terminals: Serial Communications
Type
No.
Signal Name
Function (Signal Level)
MEM OBUS/Modbus
Communication
<1>
R+
Communications input (+)
MEM OBUS/M odbus communication: U se an RS-485 or
R S-422 cable to connect the drive.
R S-485/422
MEM OBUS/Modbus
communication protocol
115.2 kbps (max.)
R-
Communications input (-)
S+
Communications output (+)
S-
Communications output (-)
IG
Shield ground
0 V
<1> Enable the term ination resistor in the last drive in a MEM OBUS netw ork by setting D IP switch S2 to the ON position. For more inform ation on
the term ination resistor, refer to
C o ntrol I/O C o nfig uratio n on page 68.
♦ Terminal Configuration
Control circuit terminals are arranged as shown in
Figure 3.18.
&
1:11 B g j n =
LJ
□
IfiL
j n f
CN
X
□E
о
§
LU
S
О
+
s
о
IG
R+
R-
S+
S-
Ш Ш Ш Ш
Й
Ш
s
ob
F ig u r e 3 .1 8 C o n tr o l C irc u it T e rm in a l A r r a n g e m e n t
T
.
M3 M4 M6
s
Щ
i
V+ AC
V- A1
A2 FM AM AC P1 C1 P2
C2
M1 M2 M5
Вs i s i s i s i s i s
s
0
Щ
S1 S2
S3 S4 S5 S6
S7 S8 SN SC SP
MA MB MC
ШШЩШЩШЩШЩ
5 i Й
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
63
E
le
c
tr
ic
a
l
In
s
ta
ll
a
ti
o
n