4.8 V erifying Parameter Settings and Backing Up Changes
4.8
Verifying Parameter Settings and Backing Up Changes
Use the Verify Menu to check all changes to parameter settings as a result o f Auto-Tuning.
Refer to Verifying Parameter
Changes: Verify Menu on page 85.
Save the verified parameter settings. Change the access level or set a password to the drive to prevent accidental
modification of parameter settings.
♦ Backing Up Parameter Values: o2-03
Setting o2-03 to 1 saves all parameter settings before resetting o2-03 to 0. The drive can now recall all the saved
parameters by performing a User Initialization (A1-03 = 1110).
No.
Parameter Name
Description
Setting Range Default Setting
o2-03
User Parameter
Default Value
Lets the user create a set o f default settings for a User Initialization.
0: Saved/Not Set
1: Set Defaults - Saves current parameter settings as the default values for a User Initialization.
2: Clear A ll - Clears the currently saved user settings. After saving the user parameter set value, the items o f
1110 (User Initialization) are displayed in A 1-03 (User Parameter Default Value).
0 to 2
0
A1-03
Initialize Parameters
Selects a method to initialize the parameters.
0: N o Initialize
1110: User Initialization (The user must first program and store desired settings using parameter o2-03)
2220: 2-Wire Initialization (parameter initialized prior to shipment)
5550: oPE4 Fault reset
0 to 2220, 5550
0
♦ Parameter Access Level: A1-01
Setting the Access Level for “Operation only” (A1-01 = 0) allows the user to access parameters A 1-D D and U D -D D
only. Other parameters are not displayed.
Setting the Access Level for “User Parameters” (A1-01 = 1) allows the user to access only the parameters that have been
previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific
application.
No.
Parameter
Name
Description
Setting
Range
Default
A1-01
A ccess Level
Selection
Selects w hich parameters are accessible via the digital operator.
0: Operation only. A 1-01, A 1-04, and A 1-06 can be set and monitored, and U D -П П parameters can also be viewed.
1: User Parameters. Only recently changed parameters from application parameters A2-01 to A 2-16 and A 2-17 to A 2-32
can be set and monitored.
2: Advanced A ccess L evel. A ll parameters can be set and monitored.
0 to 2
2
A2-01
to
A2-32
User Parameters
1 to 32
Parameters selected by the user are saved as User Parameters, including recently view ed parameters and parameters
specifically selected for quick access.
I f parameter A2-33 is set to 1, recently view ed parameters w ill be listed between A 2-17 and A 2 -3 2 . Parameters A2-01
through A 2-16 must be manually selected by the user.
If A 2-33 is set to 0, recently view ed parameters w ill not be saved to the group o f User Parameters. A 2 - D D parameters
are now available for manual programming.
A 1-00 to
o4-13
-
A2-33
User Parameter
Automatic Selec
tion
0: Parameters A2-01 through A 2-32 are reserved for the user to create a list o f User Parameters.
1: Save history o f recently view ed parameters. Recently edited parameters w ill be saved to A 2-17 through A 2-32 for
quick access. The m ost recently changed parameter is saved to A 2-17. The second m ost recently changed parameter is
saved to A2-18.
0, 1
1
♦ Password Settings: A1-04, A1-05
The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to
unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following
parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01,
A1-02, A1-03 and A2-01 through A2-33.
N ote: Param eter A1-05 is hidden from view. To display A 1-05, access param eter A 1-04 and press
^ 3 and J simultaneously.
130