YASKAWA
TOEPC710616134G AC Drive L1000A Technical Manual Addendum
15
◆
Added and Modified Parameters for DI-A3 Multi-Functional Support
Table 3.1 Added and Modified Parameters
Parameter
MEMOBUS
Address (Hex.)
Operator Display
[Parameter Name]
Description
Range
[Default]
F3-01
390
DI-A3 Opt InpSel
[DI-A3 Option Input Selection]
Option Card Input Selection
Select the method to input the option card data.
0 : BCD 1% unit
1 : BCD 0.1% unit
2 : BCD 0.01% unit
3 : BCD 1 Hz unit
4 : BCD 0.1 Hz unit
5 : BCD 0.01 Hz unit
6 : BCD custom setting (5 digit input), 0.02 Hz units
7 : Binary input
8 : Multi-Functional
0 - 8
[8]
F3-04
619
DI-A3 D0 FuncSel
[Terminal D0 Function Selection]
Terminal function selection for DI-A3 option input. Same setting
range as H1-03 to H1-08.
0 - 79 (Hex.)
[0F (Hex.)]
F3-05
61A
DI-A3 D1 FuncSel
[Terminal D1 Function Selection]
F3-06
613
DI-A2 D2 FuncSel
[Terminal D2 Function Selection]
F3-07
614
DI-A3 D3 FuncSel
[Terminal D3 Function Selection]
F3-08
615
DI-A3 D4 FuncSel
[Terminal D4 Function Selection]
F3-09
616
DI-A3 D5 FuncSel
[Terminal D5 Function Selection]
F3-10
617
DI-A3 D6 FuncSel
[Terminal D6 Function Selection]
F3-11
618
DI-A3 D7 FuncSel
[Terminal D7 Function Selection]
◆
Added Faults and Alarms for DI-A3 Multi-Functional Support
Table 3.2 Added Faults
Fault
Display (Hex.)
Alarm Display
[Alarm Name]
Description
OEF0 - OEF3
3C - 3F
DI-A3 Ext Fault0 - 3
DI-A3 External Fault 0 - 3
Digital Input Option DI-A3 External Fault
An external fault has been triggered on an input terminal (D0 - D7) of the DI-A3 option.
OEF4 - OEF7
64 - 67
DI-A3 Ext Fault4 - 7
DI-A3 External Fault 4 - 7
Table 3.3 Added Alarms
Alarm
Display (Hex.)
Alarm Display
[Alarm Name]
Description
OEF0 - OEF3
2C - 2F
DI-A3 Ext Fault0 - 3
DI-A3 External Fault 0 - 3
Digital Input Option DI-A3 External Alarm
An external alarm has been triggered on an input terminal (D0 - D7) of the DI-A3
option.
OEF4 - OEF7
49 - 4C
DI-A3 Ext Fault4 - 7
DI-A3 External Fault 4 - 7
4
Advanced Light Load Search
The
Advanced Light Load Search function [S4-01 = 3]
detects the load condition during normal travel operation.
Unlike search methods
1
and
2
, this function does not move the car up and down when detecting the light load
direction.
This function is also useful in applications where an excessive discharge of UPS or batteries during Light Load
Search operation shall be avoided.
When using Advanced Light Load Search in combination with a controller, it might be desired to determine the
Light Load Direction (indicated by D/O function
54h
) by the drive but to let the controller initiate the evacuation
EN
Summary of Contents for L1000A CIMR-LC F Series
Page 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Page 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Page 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Page 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Page 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...