Related Drive Parameters
These parameters set the drive for operation with the option. Make sure that the parameter settings in this table are
correct before you start network communications.
Note:
•
Hex.: MEMOBUS addresses that you can use to change parameters over network communication are represented in hexadecimal
numbers.
•
Expert: Some monitors are available in Expert Mode only. When
A1-01 = 3 [Access Level Selection = Expert Level]
, Expert Mode
monitors can be displayed on the keypad.
No.
(Hex.)
Name
Description
Default
(Range)
b1-01
(0180)
Frequency Reference
Selection 1
Selects the input method for frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
Note:
Set
b1-01 = 3
to use the controller to control the frequency reference of the drive.
1
(0 - 4)
b1-02
(0181)
Run Command Selection 1
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
7 : AUTO C Term Run
8 : AUTO C Serial Run
9 : AUTO C Option Run
Note:
•
Set
b1-02 = 3 or 9
to start and stop the drive with the controller using serial
communications.
•
The setting range and selections are different for different drives. Refer to the instruction
manual of your specific drive for more information.
1
(0 - 9)
F6-01
(03A2)
Communication Error
Selection
Selects drive response when the drive detects a
bUS [Option Communication Error]
error during
communications with the option.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use
C1-09
)
3 : Alarm Only
4 : Alarm (Run at
d1-04
)
5 : Alarm - Ramp Stop
Note:
•
When you set this parameter to
3
or
4
, the drive will continue operation after it detects a
fault. Separately prepare safety protection equipment and systems, for example fast-stop
switches.
•
Refer to the drive manual to know if settings
4
and
5
are available.
•
The setting range for Z1000U drive is different for different software versions. Refer to the
Peripheral Devices & Options section of the drive instruction manual for more information.
•
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
1
(0 - 5)
F6-02
(03A3)
Comm External Fault (EF0)
Detect
Selects the conditions at which
EF0 [Option Card External Fault]
is detected.
0 : Always Detected
1 : Detected during RUN Only
0
(0, 1)
F6-03
(03A4)
Comm External Fault (EF0)
Select
Selects the operation of the drive when
EF0 [Option Card External Fault]
is detected.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When you set this parameter to
3
, the drive will continue operation after it detects a fault.
Separately prepare safety protection equipment and systems, for example fast stop switches.
1
(0 - 3)
F6-07
(03A8)
Multi-Step Ref @ NetRef/
ComRef
Sets the function that enables and disables the multi-step speed reference when the frequency
reference source is NetRef or ComRef (communication option or MEMOBUS/Modbus
communications).
0 : Disable Multi-Step References
1 : Enable Multi-Step References
0
(0, 1)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Selects whether communication-related parameters
F6-xx and F7-xx
are set back to original
default values when you use parameter
A1-03 [Initialize Parameters]
to initialize the drive.
0 : No Reset - Parameters Retained
1 : Reset - Back to Factory Default
0
(0, 1)