
3 Conditions of Acceptability
YASKAWA ELECTRIC
TOBP C710606 40A YASKAWA AC Drive - J1000 Finless Installation Manual
13
◆
J1000 Finless Drive Watt Loss Thermal Characteristics
■
Normal Duty
Table 6 Drive Watt Loss (Normal Duty Rating)
Note:
Carrier frequency is set to 2 kHz.
200 V Single-Phase Class
Model
CIMR-J
BA
0001
0002
0003
0006
0010
–
–
–
–
Rated Output Current (A)
1.2
1.9
3.3
6.0
9.6
–
–
–
–
Generated Heat
Loss
Heatsink Plate
(W)
5.0 7.6 14.6
30.1
51.7 –
–
–
–
Internal (W)
8.0
9.7
14.4
19.4
29.8
–
–
–
–
Total (W)
13.5
17.3
29.0
49.5
81.5
–
–
–
–
200 V Three-Phase Class
Model
CIMR-J
2A
0001
0002
0004
0006
0008
0010
0012
0018
0020
Rated
Output
Current
(A)
1.2 1.9 3.5 6.0 8.0 9.6 12.0 17.5 19.6
Generated Heat
Loss
Heatsink Plate
(W)
5.0 7.6 15.8 27.5 44.6 51.7 61.3 89.8 98.7
Internal
(W)
8.0 9.5 13.6 17.2 24.0 25.8 30.4 44.1 46.3
Total
(W)
13.0 17.1 29.4 44.7 68.6 77.5 91.7 133.9 145.0
400 V Three-Phase Class
Model
CIMR-J
4A
0001
0002
0004
0005
0007
0009
0011
–
–
Rated
Output
Current
(A)
1.2 2.1 4.1 5.4 6.9 8.8 11.1 –
–
Generated Heat
Loss
Heatsink Plate
(W)
10.0 18.5 30.5 44.5 58.5 63.7 81.7 –
–
Internal
(W)
9.6 13.9 16.8 21.8 28.5 31.4 46.0 –
–
Total
(W)
19.6 32.4 47.3 66.3 87.0 95.1 127.7 –
–