Input Fuse Installation
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
.
Table C.5 Factory Recommended AC Drive Branch Circuit Protection (Normal Duty)
Drive Model
Nominal
Output Power
HP
AC Drive Input
Amps
MCCB Rating
Amps
Time Delay Fuse
Non-time Delay
Fuse Rating
Bussman Semi-
conductor Fuse
Rating (Fuse
200 V Class
2A0004
0.75
3.9
15
6.25
10
FWH-70B (70)
2A0006
1 - 1.5
7.3
15
12
20
FWH-70B (70)
2A0008
2
8.8
15
15
25
FWH-70B (70)
2A0010
3
10.8
20
17.5
30
FWH-70B (70)
2A0012
3
13.9
25
20
40
FWH-70B (70)
2A0018
5
18.5
35
30
50
FWH-90B(90)
2A0021
7.5
24
45
40
70
FWH-90B(90)
2A0030
10
37
60
60
110
FWH-100B (100)
2A0040
15
52
100
90
150
FWH-200B (200)
2A0056
20
68
125
110
200
FWH-200B (200)
2A0069
25
80
150
125
225
FWH-200B (200)
2A0081
30
96
175
150
275
FWH-300A (300)
2A0110
40
111
200
175
300
FWH-300A (300)
2A0138
50
136
250
225
400
FWH-350A (350)
2A0169
60
164
300
250
450
FWH-400A (400)
2A0211
75
200
400
350
600
FWH-400A (400)
2A0250
100
271
500
450
800
FWH-600A (600)
2A0312
125
324
600
500
800
FWH-700A (700)
2A0360
150
394
700
600
1000
FWH-800A (800)
2A0415
175
471
900
800
1400
FWH-1000A (1000)
400 V Class
4A0002
1
2.1
15
3.5
6
FWH-40B (40)
4A0004
2
4.3
15
7.5
12
FWH-50B (50)
4A0005
3
5.9
15
10
17.5
FWH-70B (70)
4A0007
3
8.1
15
12
20
FWH-70B (70)
4A0009
5
9.4
15
15
25
FWH-90B (90)
4A0011
7.5
14
25
20
40
FWH-90B (90)
4A0018
10
20
40
35
60
FWH-80B (80)
4A0023
15
24
45
40
70
FWH-100B (100)
4A0031
20
38
75
60
110
FWH-125B (125)
4A0038
25
44
75
75
125
FWH-200B (200)
4A0044
30
52
100
90
150
FWH-250A (250)
4A0058
40
58
100
100
150
FWH-250A (250)
4A0072
50
71
125
110
200
FWH-250A (250)
4A0088
60
86
150
150
250
FWH-250A (250)
4A0103
75
105
200
175
300
FWH-250A (250)
4A0139
100
142
250
225
400
FWH-350A (350)
4A0165
125
170
300
250
500
FWH-400A (400)
4A0208
150
207
400
350
600
FWH-500A (500)
4A0250
200
248
450
400
700
FWH-600A (600)
4A0296
250
300
600
500
800
FWH-700A (700)
4A0362
300
346
600
600
1000
FWH-800A (800)
C.2 UL and CSA Standards
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
347
C
Standards Compliance
Summary of Contents for iQpump1000