A.1 Power Ratings
u
Three-Phase 200 V Class Drive Models 2A0004 to 2A0030
Table A.1 Power Ratings (Three-Phase 200 V Class)
Item
Specification
Drive Model
2A0004 2A0006 2A0008 2A0010 2A0012 2A0018 2A0021 2A0030
Maximum Applicable Motor
Capacity (HP)
ND Rating
0.75
1
2
3
3
5
7.5
10
Input
Input Current (A)
ND Rating
3.9
7.3
8.8
10.8
13.9
18.5
24
37
Rated Voltage
Rated Frequency
Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
ND Rating
2.2
3.1
4.1
5.8
7.8
9.5
14
18
Output
Rated Output Capacity
(kVA)
ND Rating
1.3
2.3
3
3.7
4.6
6.7
8
11.4
Rated Output Current (A)
ND Rating
3.5
6
8
9.6
12
17.5
21
30
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable between 1 and 15 kHz
Maximum Output Voltage (V)
Three-phase 200 to 240 V (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-set)
connections, and power supply impedance.
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings
raise the carrier frequency and require current derating.
A.1 Power Ratings
234
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Summary of Contents for iQpump1000
Page 355: ......