YASKAWA
TM.iQp.02 iQpump Drive Programming Manual
77
◆
H4 Analog Outputs
■
H4-01 Terminal FM Monitor Selection
Setting Range:
1 to 53
Factory Default: 2: Output Freq
The FM and AM analog output terminals can be programmed to output a 0-10 Vdc signal proportional to any one of functions detailed in
Table 18
When the H4-01 or H4-04 are configured the iQpump drive will output 10 Vdc to represent 100% of the function programmed into them.
Figure 1.73
Figure 73 Analog Output Signal Level as a Function of the Monitor Value
Function: Frequency Ref (Setting: 1)
The analog output level will correspond to the chosen Speed Command input whether it is input via the digital operator, analog input, or
serial communication. 100% will be equivalent to the maximum output frequency of the iQpump drive (E1-04).
Function: Output Freq (Setting: 2)
The analog output level will correspond to the actual Speed being output by the iQpump drive and will include the acceleration and
deceleration ramps. 100% will be equivalent to the maximum output frequency of the iQpump drive (E1-04).
Function: Output Current (Setting: 3)
The analog output level will correspond to the output current level of the Drive. 100% will be equivalent to the Drives rated output
current which is based on the kVA Rating of the iQpump drive (o2-04).
Function: Output Voltage (Setting: 6)
The analog output level will correspond to the output voltage level of the Drive. 100% will be equivalent to either 200 Vac or 400 Vac
depending on the input voltage rating of the Drive.
Function: DC Bus Voltage (Setting: 7)
The analog output level will correspond to the voltage level of the Drive’s DC Bus. 100% will correspond to 400 Vdc for the 240 Vac
input iQpump drive and 800 Vdc for the 480 Vac input Drive.
Setting
Description
Setting
Description
1
Frequency Ref
20
SFS Output*
2
Output Freq
24
PI Feedback
3
Output Current
31
Not Used
6
Output Voltage
36
PI Input
7
DC Bus Voltage
37
PI Output
8
Output kWatts
38
PI Setpoint
15
Term A1 Level
51
Auto Mode Fref
16
Term A2 Level
52
Hand Mode Fref
18
Mot SEC Current
53
PI Feedback 2
* SFS is the internal soft starter signal. This signal is generated from the reference and often it passes through the accel/ decel functions.
10 V
100%
0
Out
put
V
ol
tage
Monitor
Function Level
Summary of Contents for iQpump Series
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK...