TM.iQp.02 iQpump Drive Programming Manual
155
Figure 1.117
Figure 122
■
P3-12 Delta Setpoint Feedback Acc/Dec Changeover
Setting Range:
0.0 to 6000.0
Factory Default: 0.0
The iQpump drive can be configured for multiplex pumping operation. The acceleration (Acc) and deceleration (Dec) times can be
changed when the difference between the delta setpoint and feedback are within the programmed level in the Delta Setpoint Feedback
Acc/Dec Changeover (P3-12).
The acceleration and deceleration times during this changeover are programmed into C1-05 and C1-06, respectively.
This function is used to improve the pump regulation.
Setting P2-12 to a value of 0 will disable this function.
TIME
Output Frequency
Add Pump Delay Time P3-04
Feedback
Auto Mode Run
Multi-function
Output #40
Wait for Start
Max-Multi Level
P3-02
STOP, 0Hz
0%
OFF Mode
Start Level
P1-04
ADD PUMP 2
AUTO MODE RUN:
Start System, Incoming Run Command
Start System
Start Level Delay
P1-05
START DELAY
System
Set-Point
Add Pump Delay Time
P3-04
Multi-function
Output #41
ADD PUMP 3
PUMP 1
Multiplex Stabilize Time
P3-11
Multiplex Stabilize Time
P3-11
Lead/Lag Functions
Disabled until
stabilization timer
expires
Summary of Contents for iQpump Series
Page 1: ...iQpump Drive Programming Manual Document Number TM iQp 02...
Page 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Page 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Page 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK...