BV0006 to BV0018, 2V0006 to 2V0040, and 4V0002 to 4V0023: 0.01 A units.
2V0056 to 2V0069 and 4V0031 to 4V0038: 0.1 A units.
rated current (A) from the condition “192 (maximum value) = drive rated current (A)”
u
U5: PID Monitors
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U5-01
(0057) PID Feedback 1
PID Feedback 1
Displays the PID feedback value.
10 V: 100%
0.01%
U5-02
(0063) PID Input
PID Input
Displays the amount of PID input (deviation between PID
setpoint and feedback).
10 V: 100%
0.01%
U5-03
(0064) PID Output
PID Output
Displays PID control output.
10 V: 100%
0.01%
U5-04
(0065) PID Setpoint
PID Setpoint
Displays the PID setpoint.
10 V: 100%
0.01%
U5-05
(07D2)
PID Differential
Feedback
PID Feedback 2
Displays the 2nd PID feedback value if differential feedback is
used (H3-
oo
= 16).
10 V: 100%
0.01%
U5-06
(07D3) PID Adjusted Feedback PID Diff Fdbk
Displays the difference of both feedback values if differential
feedback is used (U5-01 - U5-05). If differential feedback is not
used, then U5-01 and U5-06 will be the same.
10 V: 100%
0.01%
U5-99
(1599) AUTO Setpoint
Auto Setpoint
Displays the PID Setpoint commanded by the source when the
drive is in AUTO Mode.
No signal output
available
0.01%
u
U6: Control Monitors
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U6-01
(0051)
Motor Secondary
Current (Iq)
Mot SEC Current
Displays the value of the motor secondary current (Iq). Motor
rated secondary current is 100%.
10 V: Motor
secondary rated
current
0.1%
u
U9: Operation Status Monitors
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U9-01
(1901) Network PID Feedback Net PI Feedback
Displays the network PID feedback recognized by the iQpump
MEMOBUS network.
No signal output
available
Dep. on
P1-02
U9-02
(1902) Network Activity
iQ Net Activity
Displays network traffic. A fluctuating number from 0 to 10000
denotes activity, while a relatively constant 0 denotes no
activity.
No signal output
available
U9-03
(1903) Time to Alternate
Time to Alternate
Displays the time remaining before a drive requests the
alternation mode set in P9-04.
No signal output
available
min
U9-04
(1904)
Running Queue
Number
Running Queue No
Displays the position in the iQPump MEMOBUS Multiplex
running queue.
No signal output
available
–
<1> Unit changes based on network status.
<->: Drive cannot communicate to other drives
<+>: Drive is a node on a network
<M>: Drive is the master on an iQpump network.
B.16 U: Monitors
376
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual