No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U3-43
(3021)
Date Month and Day
8th at Most Recent Fault Fault 8 MMDD
Displays the date and day when the eighth most recent fault
occurred.
No signal output
available
–
U3-44
(3022)
Time Hours and
Minutes at 8th Most
Recent Fault
Fault 8 HHMM
Displays the time when the eighth most recent fault occurred. No signal output
available
–
U3-45
(3023)
Date Year at 9th Most
Recent Fault
Fault 9 YYYY
Displays the year when the ninth most recent fault occurred.
No signal output
available
–
U3-46
(3024)
Date Month and Day at
9th Most Recent Fault Fault 9 MMDD
Displays the date and day when the ninth most recent fault
occurred.
No signal output
available
–
U3-47
(3025)
Time Hours and
Minutes at 9th Most
Recent Fault
Fault 9 HHMM
Displays the time when the ninth most recent fault occurred. No signal output
available
–
U3-48
(3026)
Date Year at 10th Most
Recent Fault
Fault 10 YYYY
Displays the year when the tenth most recent fault occurred.
No signal output
available
–
U3-49
(3027)
Date Month and Day at
10th Most Recent Fault Fault 10 MMDD
Displays the date and day when the tenth most recent fault
occurred.
No signal output
available
–
U3-50
(3028)
Time Hours and
Minutes at 10th Most
Recent
Fault 10 HHMM
Displays the time when the tenth most recent fault occurred.
No signal output
available
–
u
U4: Maintenance Monitors
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U4-01
(004C)
Cumulative Operation
Time
Drv Elapsed Time
Displays the cumulative operation time of the drive. The value
for the cumulative operation time counter can be reset in
parameter o4-01. Use parameter o4-02 to determine if the
operation time should start as soon as the power is switched on
or only while the Run command is present. The maximum
number displayed is 99999, after which the value is reset to 0.
No signal output
available
1 h
U4-02
(0075)
Number of Run
Commands
RUN Cmd Counter
Displays the number of times the Run command is entered.
Reset the number of Run commands using parameter o4-13.
This value will reset to 0 and start counting again after reaching
65535.
No signal output
available
1 Time
U4-03
(0067)
Cooling Fan Operation
Time
Fan Elapsed TIme
Displays the cumulative operation time of the cooling fan. The
default value for the fan operation time is reset in parameter
o4-03. This value will reset to 0 and start counting again after
reaching 99999.
No signal output
available
1 h
U4-04
(007E)
Cooling Fan
Maintenance
Fan Life Mon
Displays main cooling fan usage time as a percentage of its
expected performance life. Parameter o4-03 can be used to reset
this monitor.
Replace the fan when this monitor reaches 90%.
No signal output
available
1%
U4-05
(007C) Capacitor Maintenance
Cap Life Mon
Displays main circuit capacitor usage time as a percentage of
their expected performance life. Parameter o4-05 can be used
to reset this monitor.
Replace the capacitor when this monitor reaches 90%.
No signal output
available
1%
U4-06
(07D6)
Soft Charge Bypass
Relay Maintenance
ChgCirc Life Mon
Displays the soft charge bypass relay maintenance time as a
percentage of its estimated performance life. Parameter o4-07
can be used to reset this monitor.
Replace the soft charge bypass relay when this monitor reaches
90%.
No signal output
available
1%
U4-07
(07D7) IGBT Maintenance
IGBT Life Mon
Displays IGBT usage time as a percentage of the expected
performance life. Parameter o4-09 can be used to reset this
monitor.
Replace the IGBT when this monitor reaches 90%.
No signal output
available
1%
U4-08
(0068) Heatsink Temperature Heatsink Temp
Displays the heatsink temperature.
10 V: 100 °C
1 °C
U4-09
(003C) LED Check
LED Oper Check
Lights all segments of the LED to verify that the display is
working properly. Press the ENTER key to turn the LEDs on
and press ESC to turn the LEDs off.
No signal output
available
–
B.16 U: Monitors
374
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual