background image

Fig. 3  Digital Operator

Next, push 

2 times on the digital operator until

In this step, the iQpump is setup for a simplex pump 
application using the Pump Quick Setup menu. Apply 
power to the iQpump after all the electrical connections 
have been made and the terminal cover has been 
re-attached. At this point 

DO NOT RUN THE MOTOR

 the 

digital operator should be reading as shown below in 

Fig. 3

.

FWD LED

 

ON

RUN LED 

OFF

01 

Flashing

the digital operator shows the 

Pump Quick Setup

 Main Menu.

Next press 

to start 

the Pump Quick Setup procedure.

The Pump Quick Start Menu consists of the most important 
parameters to setup your iQpump for use with your pump system.

Press                 to access a parameter, and use 

to select the digit and use                                 to change the 

parameter value. 

                                                                    

Press                  to save the value.

Press                  to go to the next parameter to continue the Pump 

Quick Setup programming. When Quick Setup is completed, press

               to  exit the Pump Quick Setup menu and go to operation.

Note: Refer to Step 5 for a Pump Quick 

Setup Parameter Overview.

Feedback 

Value

IMPORTANT: Enter service factor amps (SFA) when using an 
iQpump with a submersible pump motor.

STOP LED 

ON

Step

1

iQpump Model Identification 

and Mounting 

To make sure you received the correct model, it is essential to 

verify the iQpump nameplate with your order and make sure 

the iQpump has the correct rating so it can be used with your 

motor. Please check the nameplate information as shown in 

the example below. 

·

Check that the available power will meet the 

input power 

requirements. 

 

·

Ensure that the 

output power from the iQpump is 

compatible with the pump motor requirements.

Mounting the iQpump

·

In the case of systems with more than one iQpump, follow 
the above procedure for each iQpump and pump motor.

Open Chassis

NEMA 1

The mounting of the iQpump is extremely important 
regarding environment and accessibility. Depending on your 
system, there are various models available and the mounting 
dimensions (footprint) may be different. Because the 
mounting procedure is fairly extensive, it is beyond the scope 
of this document; the user is referred to the iQpump User 
Manual (Document No. TM.iQp.06) received with the 
iQpump, 

Section 1 Physical Installation. Match the model 

that you received and follow the procedure described in the 
manual to ensure a safe and functional installation. In cases 
where the system has more than one iQpump, refer to the 
proper clearances required for adequate ventilation.  

Please 

pay particular attention to:   

·

The clearances to be maintained around the enclosure 
for adequate ventilation.

 

·

The environmental specifications such as avoiding 
excessive dampness, extreme temperatures, chemical 
exposure, corrosive areas, etc. to avoid damage to the 
equipment and to maintain safety. 

 

Removing and Attaching the Terminal Cover

Improper removal of the iQpump terminal cover as well as 
front cover can cause extensive damage to the iQpump. To 
avoid damage to these items, please pay particular attention 
to the iQpump User Manual, Document No. TM.iQp.06, 
Section 1.8, R

Removing and Attaching the Terminal Cover.

Drive Model 

Number

Input Power

Rating

Output Power

Rating

Serial 

Number

UL File 

Number

Drive Spec 

Number

Weight

0034

WARNING  DO NOT CONNECT ANY OF THE 

FOLLOWING TERMINALS TO EARTH GROUND

B1

B2

-

+

+1

+2

R/L1 S/L2 T/L3

-

+ 1

+ 2

B1

B2

U/T1 V/T2 W/T3

NOT USED

3Ø Induction 

motor

Use L1, L2, L3 for

3Ø Input Power

Connect 
frame to 

ground

Input

Protection

(Fuse or Circuit 

Breaker)

To change direction of 

pump motor rotation 
swap any 

two 

of the

 

three 

motor leads 

(See Step 2)

L1 L2 L3

Fig. 1 Input Power and Output Motor Electrical Connections for 
                   Models: 20P4 to 2018  and  40P4 to 4018

NOT USED

3Ø Induction 

motor

Connect 
frame to 

ground

Input

Protection

(Fuse or Circuit 

Breaker)

To change direction of pump 
motor rotation swap any 

two 

of the

 three 

motor leads 

(See Step 2)

Fig. 2 Input Power and Output Motor Electrical Connections for 
                  Models: 2022 & Larger   and   4030 & Larger

R/L1

R1/L11

S/L2

S1/L21

T/L3

T1/L31

U/T1

V/T2

W/T3

-

+

 1

+

 2

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to 

chassis 
ground

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to 

chassis 
ground

Use L1, L2 for 

1Ø Input Power

Use L1, L2, L3 for

3Ø Input Power

L1 L2 L3

Use L1, L2 for 

1Ø Input Power

Connect to 

chassis ground

Fig.1 & 2 

below show the electrical connections for the 

input power and motor terminals for various iQpump 
models.

 

Select the proper diagram for the model you are 

installing 

(see Step 1).

 

WITH POWER OFF 

make the 

appropriate connections.

Make sure to follow good wiring practices and all 
applicable codes. Ensure that the equipment is 
grounded properly as shown.

DANGER; 

LETHAL VOLTAGES ARE PRESENT- Before 

applying power to the iQpump, ensure that the 
terminal cover is fastened and all wiring connections 
are secure. After the power has been turned OFF, wait 
at least five minutes until the charge indicator 
extinguishes completely before touching any wiring, 
circuit boards or components. 

!

*

* Make sure the 

iQpump

 has been properly sized for single phase input power.

*

Connect Pump Motor and  

Line Power 

Step

2

Step

3

Control Wiring 

Step

4

Pump Quick Setup 

The following 
procedure is a 
supplement to 
other 
documentation 
supplied with this 
equipment and 
will guide the user 
in properly wiring 
the iQpump and 
motor. It will also 
show the user 
how to configure 
the iQpump for a 
simplex pump 
application.
      

Danger: 

Improper wiring 
can and will 
cause 

 

bodily 

harm as well as 
damage to the 
equipment.

When installing 
the system, be 
sure to follow 
good wiring 
practices and all 
applicable codes. 
Ensure that the 
mounting of the 
various 
components are 
secure and that 
the environment, 
such as extreme 
dampness, poor 
ventilation, etc. 
will not cause 
system 
degradation. 

Please read this 
cheat sheet and 
other 
documentation 
provided with 
the iQpump 
thoroughly 
before 
attempting any 
installation. 

 

Page 1 of 4 

iQpump 7 AC Drive 

(Software 0034)

 

Simplex Quick Start Procedure  

The iQpump is D

DEFAULT SETUP TO START/STOP FROM THE 

KEYPAD (digital operator). If this is the preferred start/stop 
method, then continue to the feedback signal connection section.  
Please refer to the wiring diagram below to start/stop the iQpump 
using an external switch or contact. 

This step shows how to connect control wiring and feedback signal 
to the iQpump. Before making any control connections, M

MAKE 

SURE POWER TO THE iQpump IS TURNED OFF! Next remove 
the terminal cover to gain access to the control terminals. (Step 1.)

SELECT START / STOP CONTROL METHOD

S3

S5 S6 S7 FM AC AM IG

S2

S4

S1

2-Wire Control

Use for permanent contacts

iQpump User Control Terminals

S+ S-

SP

A2 +V AC

AC

SC

A1

SN

R+ R-

Connect switch or contact to 
terminal S1 and terminal SN

S3

S5 S6 S7 FM AC AM IG

S2

S4

S1

3-Wire Control

Use for momentary contacts

S+ S-

SP

A2 +V AC

AC

SC

A1

SN

R+ R-

Connect momentary contacts 
to terminal S1, S2 and SN

Normally Open

Normally Closed

To use 3-Wire Control first 
initialize the iQpump using 

parameter A1-03 = 3330  

(Refer to TM.iQp.06)

FEEDBACK SIGNAL WIRING (TRANSDUCER)

S3

S5 S6 S7 FM AC AM IG

S2

S4

S1

For use with 3-Wire, 0 – 10V Transducer

iQpump User Control Terminals

S+ S-

SP

A2 +V AC

AC

SC

A1

SN

R+ R-

Brown or Red: +Power (1)

O
F
F

1

2

S1-2 in ON

Position

S3

S5 S6 S7 FM AC AM IG

S2

S4

S1

S+ S-

SP

A2 +V AC

AC

SC

A1

SN

R+ R-

Brown or Red: +Power (1)

Black or White Output 
0 – 10V (3)

O
F
F

1

2

S1-2 in OFF

Position

Blue or Black 
Common Signal (2)

Black: Output
4 – 20mA (2)

Cable 

Type

DIN

Type

For use with 2-Wire, 4 – 20mA Transducer

Important Note: Signal colors and numbering may vary 
depending on feedback device used. 
Please consult feedback device manual.

!

Cable
Shield

Cable
Shield

E(G)

E(G)

(Factory Default)

E(G)

Cable
Shield

Cable
Shield

E(G)