YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
265
■
5: Multi-Step Speed Reference 3
Setting Value
Function
Description
5
Multi-Step Speed Reference
3
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
Note:
Refer to
“
Setting Procedures for Multi-step Speed Operation
”
in
“
d: Reference Settings
”
for more information.
■
6: Jog Reference Selection
Setting Value
Function
Description
6
Jog Reference Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in
d1-17 [Jog Reference]
. The JOG Frequency Reference
(JOG command) overrides the
d1-01 to d1-08 [References 1 to 8]
settings.
■
7: Accel/Decel Time Selection 1
Setting Value
Function
Description
7
Accel/Decel Time Selection
1
Sets the drive to use
Acceleration/Deceleration Time 1 [C1-01, C1-02]
or
Acceleration/Deceleration Time 2 [C1-03, C1-04]
.
Note:
Refer to
C1: Accel & Decel Time on page 227
for more information.
■
8: Baseblock Command (N.O.)
Setting Value
Function
Description
8
Baseblock Command (N.O.)
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
The keypad flashes
bb [Baseblock]
. If you cancel the baseblock command when the Run command is active, the drive
will restart the motor and use the speed search function.
Figure 5.40 Baseblock Command Time Chart
ON : Baseblock (drive output stop)
OFF : Normal operation
■
9: Baseblock Command (N.C.)
Setting Value
Function
Description
9
Baseblock Command (N.C.)
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
The keypad flashes
bb [Baseblock]
. If you cancel the baseblock command when the Run command is active, the drive
will restart the motor and use the speed search function.
ON : Normal operation
OFF : Baseblock (drive output stop)
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...