YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
249
D002 - D016, A002 - A015, B001 - B007
D024 - D169, A022 - A154, B011 - B077
A192 - A248, B096 - B302
E : Const Trq, 60 Hz base, 180 Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007
D024 - D169, A022 - A154, B011 - B077
A192 - A248, B096 - B302
F : Custom
Set
E1-04
to
E1-13 [V/f Pattern for Motor 1]
to set the values for this custom pattern.
The default settings are the same as setting value
1 [Const Trq, 60Hz base, 60Hz max]
.
■
E1-04: Maximum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-04
(0303)
Maximum Output Frequency Sets the maximum output frequency for the V/f pattern.
60.0 Hz
(40.0 to 400.0 Hz)
■
E1-05: Maximum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-05
(0304)
Maximum Output Voltage
Sets the maximum output voltage for the V/f pattern.
208/240 V: 230.0 V,
480 V: 460.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
■
E1-06: Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
60.0 Hz
(0.0 - E1-04)
■
E1-07: Mid Point A Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-07
(0306)
Mid Point A Frequency
Sets a middle output frequency for the V/f pattern.
30.0 Hz
(0.0 - E1-04)
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...