224
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
PID Feedback Loss Go To Frequency Timeout
The drive will apply this feature only when
b5-82 = 3 [Run At b5-83]
and it detects a Feedback Loss. Parameter
b5-
85 [Feedback Loss GoTo Freq Timeout]
sets the length of time that the drive will run at the frequency set in
b5-83
[Feedback Loss GoTo Frequency]
.
•
When
b5-85 = 0 sec
, the drive will operate at the
b5-83
speed indefinitely.
•
When
b5-85 > 0 sec
, the drive will only operate at the
b5-83
speed for the time specified in
b5-85
, after which the
drive will fault on an
FDBKL [WIRE Break]
fault.
Refer to
for more information.
b5-83: Feedback Loss GoTo Frequency
b5-85: Feedback Loss GoTo Freq Timeout
b5-86: Feedback Loss Start Delay
H2-xx = B9: Transducer Loss
H3-xx = B: PID Feedback
FDBKL Fault: WIRE Break
FLGT Alarm: Feedback Loss, Go To Freq b5-83
Figure 5.28 Time Chart for the Wire Break Detection when b5-82 = 3
Backup PID Feedback Transducer Input
When you set
H3-xx = 24 [MFAI Function Selection = PID Feedback Backup]
, the drive will activate the PID
Feedback Backup signal.
•
If the primary PID Feedback (
H3-xx = B [PID Feedback]
) is lost, the system will automatically use the backup PID
Feedback from the MFAI terminal set for
H3-xx = 24
and flash a
Bu-Fb [Main Fdbk Lost Using Backup Fdbk]
alarm.
•
If the main PID Feedback is operational, but the backup PID Feedback is lost, the drive will show a
BuFbl [Backup
Fdbk Lost Chk/Repl Xducer]
alarm. If the main and backup PID Feedback devices are lost, the drive will use the
b5-82 [Feedback Loss 4
~
20mA Detect Sel]
setting.
Note:
To enable the
FDBKL [WIRE Break]
detection correctly, use a 4 to 20 mA operation in these conditions:
•
Use a 4 to 20 mA signal for transducers.
•
Program the drive analog inputs and set Jumper Switch S1 to
“
I
”
for current input.
If you set the analog input for voltage, the drive will disable the detection mechanism.
■
b5-83: Feedback Loss GoTo Frequency
No.
(Hex.)
Name
Description
Default
(Range)
b5-83
(31B1)
RUN
Feedback Loss GoTo
Frequency
Sets the speed at which the drive will run if the drive detects a 4 to 20 mA wire-break on the PID
Feedback and
b5-82 = 3 [Feedback Loss 4
~
20mA Detect Sel = Run At b5-83]
.
0.0 Hz
(0.0 - 400.0 Hz)
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...