S6-09: Emergency Override Min Speed
No.
(Hex.)
Name
Description
Default
(Range)
S6-09
(3240)
Emergency Override Min
Speed
When Emergency Override is active, the output frequency is lower-limited to this value.
0.00 Hz
(0.00 - 400.00 Hz)
Note:
When
A1-02 = 8 [Control Method Selection = EZOLV]
, the range is 0.00 to 120.00 Hz.
■
S6-10: Emergency Override Max Speed
No.
(Hex.)
Name
Description
Default
(Range)
S6-10
(3241)
Emergency Override Max
Speed
When Emergency Override is active, the output frequency is upper-limited to this value.
0.00 Hz
(0.00 - 400.00)
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, the range is 0.00 to 120.00 Hz.
•
Set this parameter to 0.00 Hz to disable the limit.
■
S6-11: EMOVR Drive Protection Fault ON
No.
(Hex.)
Name
Description
Default
(Range)
S6-11
(3242)
Expert
EMOVR Drive Protection
Fault ON
Sets the bit to enable fault detection during Emergency Override.
0
(0 - FFFF)
bit 0 : Uv1 - DC Bus Undervoltage
bit 1 : CoF - Current Offset Fault
bit 2 : dWF1 - EEPROM Memory DWEZ Data Error
bit 3 : Err - EEPROM Write Error
bit 4 : Reserved
bit 5 : Reserved
bit 6 : oL2 - Drive Overload
bit 7 : oPr - Operator Connection
bit 8 : PF - Input Phase Loss
bit 9 : Reserved
bit 10 : Reserved
bit 11 : oH - Heatsink Overheat
bit 12 : oH1 - Heatsink Overheat
bit 13 : OD - Output Disconnect
bit 14 : FAn1 - Cooling Fan Fault
bit 15 : ov2 - DC Bus Overvoltage 2
Note:
The drive sets the bits in Hex.
■
S6-12: EMOVR Motor Protection Fault ON
No.
(Hex.)
Name
Description
Default
(Range)
S6-12
(3243)
Expert
EMOVR Motor Protection
Fault ON
Sets the bit to enable fault detection during Emergency Override.
0
(0 - FFFF)
bit 0 : LF - Output Phase Loss
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV