2.11 o: Keypad-Related Settings
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
405
Table 2.62 Example of Message Displays for Pre-Charge
Default (o1-82 = 0)
Full Screen Message (o1-82 = 1)
Note:
•
When
o1-80 = 0 [OFF]
, drive Faults,
oFAxx
, or
CPFs
do not trigger a full-screen message to display.
•
When
o1-81= 0 [Alarm Screen Display = OFF]
, drive Alarms do not trigger a full-screen message to display.
•
When
o1-82 = 0 [Message Screen Display = OFF]
, drive Messages do not trigger a full-screen message to display. The keypad will
continue to show limit errors and other informative screens.
•
You cannot select the display method of
oPExx [Parameter Setting Errors]
. The keypad shows
oPExx
errors as full screen displays and
status monitor displays. Active
oPExx
errors have display priority over active faults and alarms.
Status Monitor Display
When
o1-40 = 0 [Home Screen Display Selection = Custom Monitor]
, the keypad will show the Status Monitor on
the second and third lines of the HOME screen.
•
The second line shows HOA status and other information, for example:
–
Fault/Alarm/
oPExx
/
oFAxx
codes
–
MEMOBUS Multiplex drive status
–
Information Text status
•
The third line shows information texts, for example:
–
Pre-Charge messages
–
Sleep messages
–
MEMOBUS Multiplex Staging and De-staging messages
It will also show Information Text for Sequence Timer status.
shows the examples of Status Monitor display during normal operation.