8.4 Replace Drive Cooling Fans and Circulation Fans
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
577
2.
Connect the power supply connector.
Figure 8.37 Connect the Power Supply Connector
3.
Put the cables and connector back into their initial position.
A - Hooks
B - Circulation fan
C - Cable connector
Figure 8.38 Put the Cable and Connector Back into the Drive
◆
Replace a Fan (Procedure D)
DANGER!
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized bypass. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the bypass is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases below
50 Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the bypass is
safe. If you do work on the bypass when it is energized, it will cause serious injury or death from electrical shock.
CAUTION!
Burn Hazard. Do not touch a hot drive heatsink. De-energize the drive, wait for a minimum of 15 minutes, then make
sure that the heatsink is cool before you replace the cooling fans. If you touch a hot drive heatsink, it can burn you.
NOTICE:
Use the instructions in this manual to replace the cooling fans. When you do maintenance on the fans, replace all the fans
to increase product life. If you install the fans incorrectly, it can cause damage to the drive and bypass.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...