Use this setting to install an IP20/UL Open Type drive. The applicable output current to operate the drive changes
when the ambient temperature changes:
•
-10 °C to +50 °C (14 °F to 122 °F): You can operate the drive with 100% output current without derating.
•
50 °C to 60 °C (122 °F to 140 °F): Derate the output current from 100% to 80%.
Make sure that there is 60 mm (2.4 in) minimum of space between drives or between the drive and side of the
enclosure panel.
1 : Side-by-Side Mounting
Use this setting to install more than one drive Side-by-Side. The applicable output current to operate the drive
changes when the ambient temperature changes:
•
-10 °C to +40 °C (14 °F to 104 °F): You can operate the drive with 100% output current without derating.
•
40 °C to 50 °C (104 °F to 122 °F): Derate the output current from 100% to 80%.
Make sure that there is 2 mm (0.08 in) minimum of space between drives.
2 : IP20/UL Type 1
Use this setting to install an IP20/UL Type 1 drive. The applicable output current to operate the drive changes when
the drive model and ambient temperature change:
•
For drive models 4005 and 4008 (bypass models B003 to B007)
–
-10 °C to +40 °C (14 °F to 104 °F): You can operate the drive with 100% output current without derating.
–
40 °C to 60 °C (104 °F to 140 °F): Derate the output current from 100% to 80%.
•
For drive models 4011 to 4027 (bypass models B011 to B027)
–
-10 °C to +50 °C (14 °F to 122 °F): You can operate the drive with 100% output current without derating.
–
50 °C to 60 °C (122 °F to 140 °F): Derate the output current from 100% to 80%.
•
For drive models 4034 to 4065 (bypass models B034 to B065)
–
-10 °C to +45 °C (14 °F to 113 °F): You can operate the drive with 100% output current without derating.
–
45 °C to 50 °C (113 °F to 122 °F): Derate the output current from 100% to 90%.
–
50 °C to 60 °C (122 °F to 140 °F): Derate the output current from 90% to 70%.
•
For drive models 2011 to 2273 and 4077 to 4302 (bypass models D002 to D273, A002 to A248, and B302)
–
-10 °C to +40 °C (14 °F to 104 °F): You can operate the drive with 100% output current without derating.
–
40 °C to 60 °C (104 °F to 140 °F): Derate the output current from 100% to 60%.
3 : IP55/UL Type 12
Use this setting to install an IP55/UL Type 12 drive. The applicable output current to operate the drive changes when
the ambient temperature changes:
•
-10 °C to +40 °C (14 °F to 104 °F): You can operate the drive with 100% output current without derating.
•
40 °C to 50 °C (104 °F to 122 °F): Derate the output current from 100% to 80%.
Figure 7.1 Derating for IP20/UL Open Type (L8-35 = 0)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...