6.11 Diagnosing and Resetting Faults
518
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
6.11
Diagnosing and Resetting Faults
When a fault occurs and the drive stops, do the procedures in this section to remove the cause of the fault, then re-
energize the drive.
◆
Fault and Power Loss Occur at the Same Time
WARNING!
Crush Hazard. Wear eye protection when you do work on the bypass. If you do not use correct safety equipment, it can
cause serious injury or death.
WARNING!
Electrical Shock Hazard. After the bypass blows a fuse or trips a GFCI, do not immediately energize the bypass or
operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF.
Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem,
contact Yaskawa before you energize the bypass or peripheral devices. If you do not fix the problem before you operate the bypass
or peripheral devices, it can cause serious injury or death.
1.
Supply power to the control circuit from the external 24 V input.
2.
Use monitor parameters
U2-xx [Fault Trace]
to show the fault code and data about the operating status of the
drive immediately before the fault occurred.
3.
Use the information in the Troubleshooting tables to remove the fault.
Note:
1. To find the faults that were triggered, check the fault history in
U2-02 [Previous Fault]
. To find information about drive status (such as
frequency, current, and voltage) when the faults were triggered, check
U2-03 to U2-20
.
2. If the fault display stays after you re-energize the drive, remove the cause of the fault and reset.
◆
Fault Occurs Without Power Loss
1.
Examine the fault code shown on the keypad.
2.
Use the information in the Troubleshooting tables to remove the fault.
3.
Do a fault reset.
◆
Fault Reset
If a fault occurs, you must remove the cause of the fault and re-energize the drive.
lists the different
methods to reset the drive after a fault.
Table 6.5 Fault Reset Methods
Methods
Description
Method 1
While the keypad is showing the fault or alarm code, push
(Reset) or
on the keypad.
Method 2
Switch ON the MFDI terminal set to
H1-xx = 14 [MFDI Function Select = Fault Reset]
.
Note:
The default setting for
H1-04 [Terminal S4 Function Selection]
is
14 [Fault Reset]
.
Method 3
1.
De-energize the drive main circuit power supply.
2.
Energize the drive again after the keypad display goes out.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...