YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
413
■
Y2-01: Sleep Level Type
No.
(Hex.)
Name
Description
Default
(Range)
Y2-01
(3C64)
Sleep Level Type
Sets the data source that the drive uses to know when to activate the Sleep Function.
5
(0 - 5)
0 : Output Frequency
1 : Output Current
2 : Feedback
3 : Output Speed (RPM)
5 : Output Frequency (non-PID)
Note:
•
Feedback depends on PID direction operation.
•
When the Sleep Function is active, the keypad will show the
“
Sleep
”
Alarm.
■
Y2-02: Sleep Level
No.
(Hex.)
Name
Description
Default
(Range)
Y2-02
(3C65)
RUN
Sleep Level
Sets the level that the level type set in
Y2-01 [Sleep Level Type]
must be at for the time set in
Y2-03
[Sleep Delay Time]
for the drive to enter Sleep Mode.
0.0
(0.0 - 6000.0)
When the monitor data of the level type set in
Y2-01
is less than this level for longer than the time set in
Y2-03
, the
drive will enter Sleep Mode.
Note:
•
When you set this parameter to 0.0, this function will not be active.
•
This function is active only when the drive operates in AUTO Mode.
•
When
Y2-01 = 5 [Output Frequency (non-PID)]
, the drive will disable the Sleep function when you set this parameter to 0.0.
•
When
Y2-01 ≠ 5
, the drive will set the sleep level to the largest value from
d2-02 [Frequency Reference Lower Limit]
,
Y1-06 [Minimum
Speed]
, and
Y4-12 [Thrust Frequency]
when you set this parameter to 0.0.
■
Y2-03: Sleep Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
Y2-03
(3C66)
RUN
Sleep Delay Time
Sets the delay time before the drive enters Sleep Mode when the drive is at the sleep level set in
Y2-
02 [Sleep Level]
.
5 s
(0 - 3600 s)
■
Y2-04: Sleep Activation Level
No.
(Hex.)
Name
Description
Default
(Range)
Y2-04
(3C67)
RUN
Sleep Activation Level
Sets the level above which the output frequency must increase to activate the Sleep Function when
Y2-01 = 0, 3, or 5 [Sleep Level Type = Output Frequency, Output Speed (RPM), or Output
Frequency (non-PID)]
.
0.0
(0.0 - 6000.0)
Note:
When you set this parameter to 0.0, this function will not be active, and the Sleep Function will activate above the minimum speed (largest
value from
d2-02 [Frequency Reference Lower Limit]
,
Y1-06 [Minimum Speed]
, and
Y4-12 [Thrust Frequency]
).
■
Y2-05: Sleep Boost Level
No.
(Hex.)
Name
Description
Default
(Range)
Y2-05
(3C68)
RUN
Sleep Boost Level
Sets the quantity of boost that the drive applies to the setpoint before it goes to sleep.
0.00%
(0.00 - 600.00%)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...