834
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Parameter
Motor 2 Selection
OFF (Motor 1)
ON (Motor 2)
C5-xx [Automatic Speed Regulator (ASR)]
C5-01 to C5-08, C5-12, C5-17, C5-18
C5-21 to C5-28, C5-32, C5-37, C5-38
E1-xx, E3-xx [V/f Patterns]
E2-xx, E4-xx [Motor Parameters]
E1-xx, E2-xx
E3-xx, E4-xx
F1-xx [Number of PG pulses per
Revolution]
F1-01 to F1-21
F1-02 to F1-04, F1-08 to F1-11, F1-14, F1-31 to F1-37
Note:
•
When you use 2 motors, the drive applies the protective function set in
L1-01 [Motor Overload Protection Select]
to motor 1 and motor 2.
•
You cannot switch between motors 1 and 2 during run. If you try to switch motors when they are running, it will cause a
rUn
error.
•
After you switch between encoder motors, you must wait 500 ms minimum to input a Run command. You must wait 200 ms minimum for
other control methods.
•
If you set
H1-xx=16 [Motor Switch Command]
and set different control methods in maximum output frequency to motors 1 and 2, the drive
will apply the lower of the two maximum to the two motors. The upper limit of
d1-xx [Frequency Reference]
will change. For example, the
upper limit of
d1-xx
will be 400 when you set these parameters to these values:
–
A1-02 = 2 [Control Method Selection = OLV]
–
E1-04 = 590 [Maximum Output Frequency = 590 Hz]
–
E3-01 = 3 [Motor 2 Control Mode Selection = CLV]
–
E3-04 = 400 [Motor 2 Maximum Output Frequency = 400 Hz]
■
17: Fast Stop (N.C.)
Setting Value
Function
Description
17
Fast Stop (N.C.)
Sets the command to ramp to stop in the deceleration time set in
C1-09 [Fast Stop Time]
when the input terminal is activated while
the drive is operating.
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
•
Fully stop the motor
•
Cancel the Run command
•
Cancel the fast stop command
Note:
•
To use the N.O. switch to input the fast stop command, set 15 (Fast Stop (N.O.)).
•
For details, refer to C1-09 [Fast Stop Time].
•
Set
C1-09 [Fast Stop Time]
to a correct deceleration time. If the deceleration time is too short, it can cause an overvoltage fault and failure
to stop the motor from coasting.
shows an example of how fast stop operates.
Figure 12.82 Fast Stop Time Chart
■
18: Timer Function
Setting Value
Function
Description
18
Timer Function
Sets the command to start the timer function. Use this setting with
Timer Output [H2-xx = 12]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA80U4720ABM
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...