SIEPC71061737B GA800 Drive Technical Reference
735
6 : 15.0 kHz (12.0 kHz AOLV/PM)
7 : Swing PWM1 (Audible Sound 1)
8 : Swing PWM2 (Audible Sound 2)
9 : Swing PWM3 (Audible Sound 3)
A : Swing PWM4 (Audible Sound 4)
F : User Defined (C6-03 to C6-05)
Use
C6-03 to C6-05
to set detailed setting values.
Note:
•
The carrier frequency for Swing PWM 1 is equivalent to 2.0 kHz. Swing PWM applies a special PWM pattern to decrease the audible
noise.
•
The setting range changes when the
A1-02 [Control Method Selection]
value changes:
–
3, 5, 7, 8 [CLV, OLV/PM, CLV/PM, EZOLV]
: You cannot set to
7 to A
.
–
4 [AOLV]
: You cannot set to
6, 7 to A, or F
.
–
6 [AOLV/PM]
: You cannot set to
7 to A or F
.
Table 12.35 Guidelines for Carrier Frequency Parameter Setup
Symptom
Remedy
Speed and torque are not stable at low speed.
Decrease the carrier frequency.
Speed and torque are not stable at low speed.
Decrease the carrier frequency.
Too much leakage current from the drive.
Decrease the carrier frequency.
Wiring between the drive and motor is too long.
Decrease the carrier frequency.
Note:
If the motor cable is too long, it can be necessary to decrease the carrier frequency. Refer to
for the
wiring distance and decrease the carrier frequency.
Audible motor noise is too loud.
Increase the carrier frequency. Use Swing PWM.
Note:
The default carrier frequency in ND is Swing PWM 1 (
C6-02 = 7
), with a 2 kHz base. You can increase the carrier
frequency in Normal Duty mode, but this will also decrease the drive rated current.
Table 12.36 Wiring Distance
Wiring Distance
Up to 50 m
Up to 100 m
Greater than 100 m
C6-02 [Carrier Frequency Selection]
1 to F (up to 15 kHz)
1 to 2 (up to 5 kHz), 7
1 (up to 2 kHz), 7
Note:
When
A1-02 = 5 or 6 [Control Method Selection = OLV/PM or AOLV/PM]
, the maximum cable length is 100 m (328 ft).
■
C6-03: Carrier Frequency Upper Limit
No.
(Hex.)
Name
Description
Default
(Range)
C6-03
(0225)
Carrier Frequency Upper
Limit
Sets the upper limit of the carrier frequency. Set
C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)]
to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
Setting a Fixed User-Defined Carrier Frequency
When you cannot use
C6-02
to set a carrier frequency between set selectable values, you can set the value in
C6-03
.
The carrier frequency will be fixed to the value set to
C6-03
.
When
A1-02 = 0, 1 [Control Method Selection = V/f, CL-V/f]
, set
C6-03 = C6-04 [Carrier Frequency Lower Limit]
to fix the carrier frequency.
Setting a Variable Carrier Frequency to Agree with the Output Frequency
When
A1-02 = 0, 1
, set
C6-03
,
C6-04
, and
C6-05 [Carrier Freq Proportional Gain]
as shown in
to
make the carrier frequency change linearly with the output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA80U4720ABM
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...