YASKAWA
TOEPC71061737D GA800 DRIVE INSTALLATION & PRIMARY OPERATION
95
Model
Recomm. Gauge (AWG, kcmil)
Crimp Terminal
Model
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
-, +1
+3
4H11
250 × 4P × 2
250 × 4P × 2
-
-
-
LCA250-12-X
-
-
300 × 4P × 2
-
-
LCA300-12-X
-
-
-
2/0 × 4P × 2
-
LCA2/0-12-X
-
-
-
-
4/0
LCA4/0-12-X
4H12
300 × 4P × 2
300 × 4P × 2
-
-
-
LCA300-12-X
-
-
300 × 4P × 2
-
-
LCA300-12-X
-
-
-
3/0 × 4P × 2
-
LCA3/0-12-X
-
-
-
-
4/0
LCA4/0-12-X
Table 12.3 Closed-Loop Crimp Terminals for 6-Phase/12-Pulse 400 V Class Drives (Drive Models: 4xxx) (Manufacturer:
PANDUIT Corp.)
Model
Recomm. Gauge (AWG, kcmil)
Crimp Terminal
Model
R/L1, R1/L11
S/L2, S1/L21
T/L3, T1/L31
U/T1
V/T2
W/T3
-, +1
+3
4810
2/0 × 4P (× 2)
-
-
-
-
LCA2/0-12-X
-
3/0 × 4P × 2
-
-
-
LCA3/0-12-X
-
-
4/0 × 4P × 2
-
-
LCA4/0-12-X
-
-
-
1/0 × 4P × 2
-
LCA1/0-12-X
-
-
-
-
3/0
LCA3/0-12-X
4930
3/0 × 4P (× 2)
-
-
-
-
LCA3/0-12-X
-
4/0 × 4P × 2
4/0 × 4P × 2
-
-
LCA4/0-12-X
-
-
-
1/0 × 4P × 2
-
LCA1/0-12-X
-
-
-
-
3/0
LCA3/0-12-X
4H11
4/0 × 4P (× 2)
-
-
-
-
LCA4/0-12-X
-
250 × 4P × 2
-
-
-
LCA250-12-X
-
-
300 × 4P × 2
-
-
LCA300-12-X
-
-
-
2/0 × 4P × 2
-
LCA2/0-12-X
-
-
-
-
4/0
LCA4/0-12-X
4H12
4/0 × 4P (× 2)
-
-
-
-
LCA4/0-12-X
-
300 × 4P × 2
300 × 4P × 2
-
-
LCA300-12-X
-
-
-
3/0 × 4P × 2
-
LCA3/0-12-X
-
-
-
-
4/0
LCA4/0-12-X
*1
The wire gauges for drive models 4810 to 4H12 are the recommended wire gauges when you use these drive models as a 6-Phase/12-
Pulse drive.
*2
When you use drive models 4810 to 4H12 as a 6-Phase/12-Pulse drive, remove the common bus bars on the input terminals.
*3
For use with PANDUIT Corp. heat-shrinkable tubing HSTT-series or an equivalent UL-recognized heat-shrinkable tubing rated 600 V
minimum.