914
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
■
L2-05: Undervoltage Detection Lvl (Uv1)
No.
(Hex.)
Name
Description
Default
(Range)
L2-05
(0489)
Undervoltage Detection Lvl
(Uv1)
Sets the voltage at which a
Uv1 [DC Bus Undervoltage]
fault is triggered or at which the KEB
function is activated. Usually it is not necessary to change this setting.
Determined by o2-04 and
E1-01
(200 V Class: 150 - 210 V,
400 V Class: 300 - 420 V)
NOTICE:
Damage to Equipment. When you set this parameter to a value lower than the default, you must install an AC reactor on
the input side of the power supply. If you do not install an AC reactor, it will cause damage to the drive circuitry.
Note:
If the low voltage detection level is near the lower limit value of
L2-05
, the drive will detect
Uv1
during KEB Ride-Thru operation. Do not
set the value too low when you use the KEB Ride-Thru function.
■
L2-06: Kinetic Energy Backup Decel Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-06
(048A)
Expert
Kinetic Energy Backup
Decel Time
Sets the deceleration time during KEB operation used to decrease the maximum output frequency to
0.
0.0 s
(0.0 - 6000.0 s)
Set
L2-29 = 2 or 3 [Kinetic Energy Backup Method = System KEB Ride-Thru 1 or System KEB Ride-Thru 2]
to
enable this function. When
L2-29 = 1, 2 , 3 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2, System
KEB Ride-Thru 1, System KEB Ride-Thru 2]
and you do KEB Auto-Tuning, the drive will automatically set this
value.
Sets the deceleration time necessary to decelerate from the frequency reference to 0 Hz when the drive detects a
momentary power loss. If a
Uv1 [DC Bus Undervoltage]
fault occurs during KEB operation, decrease the
deceleration time. If an
ov [Overvoltage]
fault occurs, increase the deceleration time.
•
L2-06 = 0
The drive automatically decreases
C1-09 [Fast Stop Time]
to the base value to keep the DC bus voltage above the
low voltage detection level. The drive ignores
L2-02 [Momentary Power Loss Ride-Thru Time]
in this condition.
•
L2-06 ≠ 0
As shown in
, the frequency reference decelerates to the KEB frequency level as specified by the
deceleration rate set in
L2-06
and then returns to the initial frequency reference as specified by
C1-01 [Acceleration
Time 1]
. The drive uses the setting value of the KEB frequency rate as shown in the this formula to set the KEB
frequency level:
KEB frequency level = Output frequency before power loss × (1 -
(L2-02)
/
(L2-06)
)
Figure 12.129 Kinetic Energy Backup Decel Time
■
L2-07: Kinetic Energy Backup Accel Time
No.
(Hex.)
Name
Description
Default
(Range)
L2-07
(048B)
Expert
Kinetic Energy Backup
Accel Time
Sets the acceleration time to return the frequency to the frequency reference before a power loss after
canceling KEB operation.
0.0 s
(0.0 - 6000.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...