H1-xx = 75, 76 [Up 2 Command, Down 2 Command]
If you set them at the same time, the drive will detect
oPE03 [Multi-Function Input Setting Err]
.
■
20 to 2F: External Fault
Setting Value
Function
Description
20 to 2F
External fault
Sets a command to stop the drive when a failure or fault occurs on an external device.
If an external fault is input to the drive, the keypad will show
EFx [External Fault (Terminal Sx)]
, where x is the
number of the terminal (terminal Sx) to which the external fault signal is assigned. For example, when an external
fault signal is input to terminal S3, the keypad will show EF3.
Use these conditions to select the value to set in
H1-xx
:
•
Signal input method from peripheral devices
•
External fault detection method
•
Motor stopping method (operation after external fault detection)
shows the relation between the conditions and the value set to
H1-xx
.
Table 12.58 Stopping Methods for External Fault
Setting
Signal Input Method from
Peripheral Devices
External Fault Detection Method
Stopping Method
N.O.
N.C.
Always
Detected
Detected during
RUN Only
Ramp to Stop
(Fault)
Coast to Stop
(Fault)
Fast Stop
(Fault)
Continuous
Operation
(Alarm Only)
20
x
-
x
-
x
-
-
-
21
-
x
x
-
x
-
-
-
22
x
-
-
x
x
-
-
-
23
-
x
-
x
x
-
-
-
24
x
-
x
-
-
x
-
-
25
-
x
x
-
-
x
-
-
26
x
-
-
x
-
x
-
-
27
-
x
-
x
-
x
-
-
28
x
-
x
-
-
-
x
-
29
-
x
x
-
-
-
x
-
2A
x
-
-
x
-
-
x
-
2B
-
x
-
x
-
-
x
-
2C
x
-
x
-
-
-
-
x
2D
-
x
x
-
-
-
-
x
2E
x
-
-
x
-
-
-
x
2F
-
x
-
x
-
-
-
x
*1
Set the terminal to N.O. (detects external fault when switched ON) or N.C. (detects external fault when switched OFF).
*2
Set the drive to always detect each fault or to detect only during run.
■
30: PID Integrator Reset
Setting Value
Function
Description
30
PID Integrator Reset
Sets the command to reset and hold the PID control integral to 0 when the terminal is ON.
Note:
Refer to
“
PID control block diagram
”
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...