Setting Parameter
Encoder Option Card
PG-B3
PG-X3
PG-F3
PG-RT3
F1-52
-
-
x
-
Number of cards that can be
installed in a drive
2
2
1
1
*1
Parameters set when using the Closed Loop V/f Control method.
*2
Parameters to set an option card connected to CN5-B.
■
F1-01: Encoder 1 Pulse Count (PPR)
No.
(Hex.)
Name
Description
Default
(Range)
F1-01
(0380)
Encoder 1 Pulse Count
(PPR)
Sets the number of output pulses for each motor revolution.
1024 ppr
(1 - 60000 ppr)
■
F1-02: Encoder Signal Loss Detect Sel
No.
(Hex.)
Name
Description
Default
(Range)
F1-02
(0381)
Encoder Signal Loss Detect
Sel
Sets the method to stop the motor or let the motor continue operating when the drive detects
PGo
[Encoder (PG) Feedback Loss]
.
1
(0 - 4)
If the drive does not detect ouput pulses from the encoder for the time set in
F1-14 [Encoder Open-Circuit Detect
Time]
, it will trigger
PGo
.
Note:
•
Motor speed and load conditions can cause
ov [Overvoltage]
and
oC [Overcurrent]
faults.
•
In AOLV control, set
n4-72 = 1 [Speed Feedback Mode = With Encoder]
.
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-
MC turns OFF.
1 : Coast to Stop
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in
C1-09 [Fast Stop Time]
. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows
PGo
and the drive continues operation. Only use this setting in special conditions to prevent
damage to the motor and machinery. The output terminal set for
Alarm [H2-01 to H2-03 = 10]
activates.
4 : No Alarm Display
The drive continues operation and does not show
PGo
on the keypad. Only use this setting in special conditions to
prevent damage to the motor and machinery.
■
F1-03: Overspeed Detection Selection
No.
(Hex.)
Name
Description
Default
(Range)
F1-03
(0382)
Overspeed Detection
Selection
Sets the method to stop the motor or let the motor continue operating when the drive detects
oS
[Overspeed]
.
1
(0 - 3)
When the motor speed is more than the value set in
F1-08 [Overspeed Detection Level]
for longer than the time set in
F1-09 [Overspeed Detection Delay Time]
, the drive will detect
oS
.
0 : Ramp to Stop
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...