11.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
594
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
No.
Name
Range
Unit
Control Method (A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
CLV/PM
(7)
EZOLV
(8)
L2-31
KEB Start Voltage
Offset Level
0 - 100
1 V
50
50
50
50
L3-05
Stall Prevention during
RUN
0 - 3
1
2
-
-
3
L3-20
DC Bus Voltage
Adjustment Gain
0.00 - 5.00
0.01
0.65
0.65
0.65
0.65
L3-21
OVSuppression Accel/
Decel P Gain
0.10 - 10.00
0.01
1.00
1.00
1.00
1.00
L3-36
Current Suppression
Gain@Accel
0.0 - 100.0
0.1
-
-
-
-
L4-01
Speed Agree Detection
Level
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
0.0 Hz
L4-02
Speed Agree Detection
Width
0.0 - 20.0
0.1
2.0 Hz
4.0%
4.0%
2.0Hz
L4-03
Speed Agree Detection
Level(+/-)
-400.0 - +400.0
0.1
0.0 Hz
0.0%
0.0%
0.0 Hz
L4-04
Speed Agree Detection
Width(+/-)
0.0 - 20.0
0.1
2.0 Hz
4.0%
4.0%
2.0Hz
L8-38
Carrier Frequency
Reduction
0 - 2
1
0
-
0
0
L8-40
Carrier Freq Reduction
Off-Delay
0.00 - 2.00
0.01 s
0.00
-
0.00
0.00
L8-90
STPo Detection Level
(Low Speed)
0 - 5000
1
0
80
-
0
n1-15
PWM Voltage Offset
Calibration
0 - 2
1
1
1
1
1
n5-04
Speed Response
Frequency
0.00 - 500.00
0.01 Hz
-
20.00
50.00
-
n8-35
Initial Pole Detection
Method
0 - 2
1
0
1
1
-
n8-51
Pull-in Current @
Acceleration
0 - 200
1%
50%
-
-
80%
o1-03
Frequency Display Unit
Selection
0 - 3
1
2
2
2
0
o1-04
V/f Pattern Display Unit 0 - 1
1
-
1
1
0
*1
The default setting is different for different models.
•
2138 - 2415, 4089 - 4720: 0.30
*2
The unit of measure changes when
o2-04
changes.
*3
The setting range is 0.0 to 100.0 when
A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector]
.
*4
The setting range is 0.0 to 40.0 when
A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector]
.
*5
The default setting changes when the setting for
C6-01 [Normal / Heavy Duty Selection]
changes.
*6
This is the value for 200 V class drives. Double the value for 400 V class drives.
*7
The default settings are different for different motor types.
•
E9-01 = 0 [Motor Type Selection = Induction (IM)]: 1
•
E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]: 4
*8
The setting range is -100.0 to +100.0 when
A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector]
.
*9
The default settings are different for different motor types.
•
E9-01 = 0 [Motor Type Selection = Induction (IM)]: 0
•
E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]: 1
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...