Make sure that there is 2 mm (0.08 in) minimum of space between drives.
2 : IP20/NEMA Type 1/IP55
Derates the drive rated output current from "-10 °C to 40 °C 100%" to "40 °C 100%" to "50 °C 85%". Use this setting
to install IP55/UL Type 12 Heatsink External Mounting drives.
3 : Finless
Derates the drive rated output current from "-10 °C to 40 °C 100%" to "40 °C 100%" to "50 °C 85%". Use this setting
to install a finless drive.
A -
L8-35 = 0
B -
L8-35 = 2
,
L8-35 = 3
C -
L8-35 = 1
Figure 10.1 Derating Depending on Drive Installation Method
◆
Altitude Derating
Install the drive in a location that has an altitude of 1000 m (3281 ft) or lower.
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 to 4000 m (3281
to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
•
Installing the drive at 2000 m (6562 ft) or lower
•
Installing the drive between 2000 to 4000 m (6562 to 13123 ft) and grounding the neutral point on the power
supply.
If you do not ground the drive with a neutral network, contact Yaskawa or your nearest sales representative.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...